background image

87045 LIMOGES Cedex

Telephone: (+33) 05 55 06 87 87 - Fax: (+33) 05 55 06 88 88

Technical data sheet: F01121EN/00

Catalogue number(s):  488 43

Updated on: 

Created on: 22/09/2010

1/3

Controller - 4 x 1-10 V outputs

CONTENTS

CONTENTS                            

  Page

1.   Use . . . . . . . . . . . . . . . . . . . . . . . . . . . .1
2. Technical features  . . . . . . . . . . . . . . . .1
3. Overall dimensions. . . . . . . . . . . . . . . .2
4. Connection . . . . . . . . . . . . . . . . . . . . . .2
5. Installation  . . . . . . . . . . . . . . . . . . . . . .2
6.  Parameter setting . . . . . . . . . . . . . . . . .3
7. Maintenance. . . . . . . . . . . . . . . . . . . . .3
8. Standards . . . . . . . . . . . . . . . . . . . . . . .3

1

2

3

4

Red indicator: 
indicates that the capacity of 
the 

 or 

 BUS 

has been exceeded 

LEARN indicator: 
indicates the learning 
or RESET phase

Indicators  
(on if output 
activated)

Control 
buttons

LEARN button

  

230 V~

4 x 1000 VA

4 x 4.3 A

4 x 1000 VA

4 x 4.3 A

4 x 1000 W

4 x 4.3 A

110 V~

4 x 500 VA

4 x 500 VA

4 x 500 W

Voltage: 100-240 V~
Frequency: 50/60 Hz
No load power consumption: 4 W

Wiring:
- Power:

Power supply: 2 x 2.5 mm

2

 (screw terminals)

N   L1: via normally open relay contact
N   L2: via normally open relay contact
N   L3: via normally open relay contact
N   L4: via normally open relay contact
0 - 10 V 

 1.5 mm

2

- Control:

Connection between detector and controller: RJ 45 cord or cable or  
BUS/SCS cable to be fitted with RJ 45 connector  
(

 150 m max. cord or BUS/SCS cable between the 

controller and the furthest detector) 
(

 500 m max. cord or BUS/SCS cable between the power supply 

and the furthest product) 

The product incorporates positive safety
-  If there is a peripheral fault on the 

 or 

 BUS, the lights 

come back on automatically after 10 minutes.

-  If there is a connection fault on the 

 BUS, the lights come back on 

automatically after 50 seconds.

Product installation: in a suspended ceiling or on a suitable cable tray

Peripherals compatible with the offer:
-  Digital detectors: infrared, ultrasound or dual technology
-  Pushbutton lighting controls: switch and scenario management 

multifunction controls| 

Usage temperature: -5°C to +45°C
Storage temperature: -20°C to +70°C
Weight: 580 g
Impact resistance: IK04
Penetration by solid and liquid matter: IP20

 + 

 + 

 + 

 

 200 mA

1. USE

This device is a power unit used for managing lighting loads.
It must be connected to one or more detectors and/or diverted 
auxiliary controls in order to operate.

The load(s) can be controlled manually or automatically by the 
detectors and/or the controls associated with the device.

2. TEChNiCal fEaTUrES

4

3

1

2

4

4

1

 

Fluorescent tubes

2

 

Tungsten halogen bulbs

3

 

Compact fluorescent bulbs

4

 

Ballasts 1 - 10 V

Reviews: