background image

20

®

9 Technical features

CONSTRUCTION SPECIFICATIONS

3 100 06

3 100 20

3 100 07

3 100 08

Weights

13 Kg

15 Kg

22 Kg

24 Kg

Dimensions L x H x P in mm

242 x 169 x 361

242 x 169 x 464

Protection

Electronic protection against overloading 

and short-circuiting. Shutdown on reaching 

operating limit and overheating.

Automatic shutdown due to protection 

triggering

Ambient specifications
Operating temperature range

from 0 to +40 °C

Operating relative humidity range

from 0 to 95% non-condensing

Degree of protection as per IEC529

IP20

Noise level at 1 meter

< 40 dBA

Electrical input specifications
Rated input voltage

230 V

Range of input voltage

from 160 V to 290 V

Rated input frequency

50-60 Hz +/-3Hz

Maximum input current

4 Arms

6 Arms

8 Arms

12 Arms

Number of input phases

Single phase

Waveform on output
With battery operation

sinusoidal

Type of operation

line interactive

Electrical specifications on output
Rated output voltage

230 V ± 10 %

Active output capacity on nominal load

600W

900W

1.2 kW

1.8 kW

Apparent output capacity on nominal load

1kVA

1.5kVA

2kVA

3kVA

Overload capacity

110% for 10 minutes of mains operation

Number of phases on output

Single phase

Summary of Contents for 310006

Page 1: ... S 1 1 5 2 3 kVA Index 1 Introduction 14 2 Conditions of use 14 3 Installation 15 4 Signals and controls 15 5 Overload and automatic shutdown 16 6 Features 16 7 Changing batteries 18 8 Possible malfunctioning 19 9 Technical features 20 ...

Page 2: ...ains plug is disconnected there are no parts inside that the user can repair The UPS Niky S has been designed to work in closed clean rooms where there are no inflamma ble liquids or corrosive substances and where it is not too damp Do not place near equipments that generate strong electro magnetic fields and or near equi pments that are sensible to electro magnetic fields engines floppy disks spe...

Page 3: ... is completely charged but in this case back up time available during black out will be shorter Light signals The color of the LEDs on the front panel has the following meanings Fixed green LED mains present and regular batteries recharging Green LED flashing every 3 sec running on battery Green LED flashing every 0 5 sec autonomy in reserve Green red LEDs flashing test or restart after end of aut...

Page 4: ...e mains on press the ON button for at least 3 seconds to perform the battery test if the batteries are working correctly the UPS will switch to battery operation for 10 seconds and then return to mains operation In case of batteries below the minimum charge level the battery LED will flash for 5 seconds if there are exhausted batteries or batteries needing replacing the battery LED will stay on Bu...

Page 5: ... Software connection Niky S 1 1 5 2 3 kVA The UPS is equipped with a USB and an RS232 interface thanks to which it is possible by means of a computer to access a set of data regarding the operation of the UPS and control the operating system unattended shutdown Software is available as on option for Win98 ME 2000 Novell and Linux from the website www ups legrand com without charge User license is ...

Page 6: ...ruptible power supply 2 Unplug the power cable from the mains socket 3 Change the batteries with others of the same type and make or having the same features Keep clear from fire to avoid explosion while handling batteries Do not open or tamper with the battery case because it contains toxic electrolyte that could be harmful for your skin or eyes Keep out of children s reach NOTICE The batteries m...

Page 7: ...tery mode it shuts down or immediately signals it is close to the operating limit The UPS has operated with no mains voltage for a long time and has not been able to recharge the battery Recharge it for at least 6 hours by connecting the uninterruptible power supply to the mains The battery is flat due to not using the UPS for a long period Recharge it for at least 6 hours by connecting the uninte...

Page 8: ...ing Degree of protection as per IEC529 IP20 Noise level at 1 meter 40 dBA Electrical input specifications Rated input voltage 230 V Range of input voltage from 160 V to 290 V Rated input frequency 50 60 Hz 3Hz Maximum input current 4 Arms 6 Arms 8 Arms 12 Arms Number of input phases Single phase Waveform on output With battery operation sinusoidal Type of operation line interactive Electrical spec...

Page 9: ... load 5 min 5 min Charging time 4 hours at 90 of the charge Technical data and number of batteries n 2 mainte nance free sealed lead bat tery 12V 7 2 Ah n 2 mainte nance free sealed lead battery 12V 9 Ah n 2 mainte nance free sealed lead acid battery 12V 7 2 Ah n 2 mainte nance free sealed lead acid battery 12V 9 Ah Standards Electromagnetic compatibility Emission Immunity Conforms to EN 62040 2 S...

Page 10: ...rew 8 Batteries exhausted notification 9 Bypass notification 10 Mains voltage low notification 11 Mains voltage too high notification 12 UPS output present notification 13 Wrong ground connection notification 14 Overload notification 15 Battery charge percentage notification 16 Battery charge selection button notification 17 RJ45 Port 18 DIP Switch 19 USB interface socket 20 RS232 serial interface...

Reviews: