KEOR TOWER SPE
Installation and User Manual
50
•
Load KVA
•
Load KW
•
Load Percentage
•
Environment Temperature
•
Total capacity of installed batteries (in external). Not visible in case the UPS is not
expandable
Setup Entries
FUNCTION
DESCRIPTION
SET + OUT + V
Output voltage (200/208/220/230/240). Default value: 230V.
SET +
Buzzer on/off. Default value: ON.
SET + LOAD 1
Manually turn on/off Load 1 bank. Default: ON
SET + LOAD 2
Manually turn on/off Load 2 bank. Default: ON
SET + BATT + AH
Total capacity of installed batteries (in external),
expressed in Ah.
Option: Ato, and nn Ah
nn is the Ah of user selected battery.
Ato enables the EBC auto detection.
If the UPS is not expandable, this parameter will be hidden
SET + IN + OUT
Auto Restart on/off. Default: ON
SET
EPO/ROO Setting for NO/NC
There are two pages for this setting:
The main page is the selection for ‘EPO’ or ‘ROO’
The subpage is the selection for the NO/NC
Use the ENTER/ESC button to enter/exit the main/sub page