45
Installation manual
Protection unit MP6-Megabreak
®
2. Signalling of protection unit state
LED 1
LED 2
T
10.25
07/10/2009
0
50
100
120
In 1800A 1200A 1500A 1500A
signalling:
an alarm is more important than a prealarm. The overload is more important than over
temperature.
Protection
Led 1
Led 2
Inactive
Switched off
Switched off
Active (I≥100A or supplied)
Green Fix
Switched off
Active: (overload
pre alarm (I>0,9Ir)
Green Fix
Rouge Fix
Active: (overload
alarm I>1,05Ir)
Green Fix
Rouge Flashing
Active: over temperature
alarm (T>75°C)
Green Flashing
Rouge Flashing