Legrand PDU User Guide 253
To replace the current script, click Load Local File or Load Example to select a new script.
To delete a script:
1. Choose Device Settings > Lua Scripts.
2. Click the desired one in the scripts list.
3. Click
> Delete.
4. Click Delete on the confirmation message.
To return to the scripts list:
Click "Lua Scripts" on the top of the page.
Or click "Lua Scripts" in the
Menu
(on page 92).
Miscellaneous
If a Cisco
®
EnergyWise energy management architecture is implemented in your place, you can enable the
Cisco EnergyWise endpoint implemented on the Legrand PDU so that this Legrand PDU becomes part of
the Cisco EnergyWise domain.
In addition, if you have to prevent others from accessing your Legrand PDU via USB-A for security reasons,
you can disable all of USB-A ports on the Legrand PDU. By default, USB-A ports are enabled.
Important: Disabling USB-A ports will disable all of 'USB-A' based features, such as wireless networking, USB
cascading or pdView access using iOS mobile devices. Therefore, re-think about it before disabling USB-A.
To configure either feature, choose Device Settings > Miscellaneous.
To set the Cisco EnergyWise configuration:
1. Select the Enable EnergyWise checkbox.
2. Configure the following:
Field
Description
Domain name
Type the name of a Cisco EnergyWise domain where
the Legrand PDU belongs
Up to 127 printable ASCII characters are permitted.
Spaces and asterisks are NOT acceptable.
Domain password
Type the authentication password (secret) for entering
the Cisco EnergyWise domain
Up to 127 printable ASCII characters are permitted.
Spaces and asterisks are NOT acceptable.
Port
Type a User Datagram Protocol (UDP) port number for
communications in the Cisco EnergyWise domain.
Range from 1 to 65535.
Default is 43440.
Polling interval
Type a polling interval to determine how often the
Legrand PDU is queried in the Cisco EnergyWise
domain.
Range from 30 to 600 ms.
Default is 180 ms.
3. Click Save in the
EnergyWise
section.