6/7

CONTENTS

Technical data sheet: S000072383EN-2 

Updated: 17/10/2017 

Created: 04/10/2012

Catalogue number(s): 0 488 17

Corridor sensor - PIR

Sensor parameters

Default 

value

Modifiable  

parameters

Configuration  

tools

0 882 30 0 882 35

Time delay

10 min

3, 5, 10, 15, 20 min

0 - 59 min 59 s

Sensitivity

PIR  

(very high)/

US (high)

Low, medium, 

high, very high

Modes

Auto on/ 

Auto off

Inactive

Activate/

Deactivate

Walk-through 

mode

Active

Activate/

Deactivate

Manual on/

Auto off

Inactive

Activate/

Deactivate

Detection  system

Initial

PIR and US PIR and/or US, 

PIR, US

Maintain

PIR or US

PIR and/or US, 

PIR, US

Restart

PIR or US

PIR and/or US, PIR, 

US, Deactivate

Alarm

Inactive

Activate/

Deactivate

  8. SETTINGS

8.1   Detection parameters

   Time  delay: Length of time the load is on after detection. 

Pulse mode (= push-button mode): If the time delay parameter is  

at 0, the sensor is in push-button mode. In this case, there is a 10 minute 

time delay before the load is switched off. If the setting is overridden or 

there is a new detection, the 10 minute time delay starts again. 

Available with configuration tool 0 882 30.

 Sensitivity: Detection range setting.

Modes:

 Auto on/Auto off mode: 

Automatic switch-on: 

- On detection of presence if the natural light level is insufficient. 

Automatic switch-off: 

- If no presence is detected and at the end of the set time delay 

- Or if the natural light level is sufficient (regulation activated)

Another detection causes automatic switch-on if there is insufficient 

light.

 Walk-through mode:

-  If no presence is detected in the 20 seconds following an initial 

detection, the product will cut off the load after 3 minutes.

-  If another presence is detected in the 3 minutes following initial 

detection, the device will cut off the load at the end of the set time 

delay.

 Manual on/Auto off mode: 

Manual switch-on, automatic switch-off: 

-  When no presence is detected and at the end of the set time delay.
After switch-off, any new detection within a 30 second period triggers 

an automatic switch-on. The Restart function must be activated.

After 30 seconds the device is switched on via a manual switch.

   8.  SETTINGS (continued)

  8.1  Detection parameters (continued)
Detection system:
Initial detection:
 The load is switched on as soon as the first detection 

occurs if the natural light level is below the light level threshold.
Maintain: The load remains active if another presence is detected.
Restart: In manual mode. After switch-off, any new detection within a 

30 second period triggers an automatic switch-on.

After 30 seconds the device must be switched on manually. 

Possible in Manual on/Auto off mode only.
Alarm: An audible signal is emitted before switch-off (1 minute before, 

then 30 seconds, then 10 seconds).

8.2   Light parameters

  Light level threshold: Value at which the load comes on if the 

natural light level is less than the setting.

  Eye function: Value 0 (eye on configuration tool 0 882 30) is 

used to save the ambient light level in the room as a light level 

threshold.

Advanced mode:

    Calibration: The ambient light level measured with a luxmeter 

must then be transmitted to the detector.

   Regulation: Automatic switch-off of the load 10 minutes after the 

light level threshold is exceeded with an additional safety threshold 

(to avoid lights switching off at the wrong moment).

Light contribution: Quantity of additional lux provided by the load 

being switched on.  

When the light contribution parameter is set to "Auto" on the 

configuration tool Cat. No. 0 882 30 the sensor automatically calculates 

the light contribution.
 8.3 Modifying the parameters using the configuration tools

• 0 882 35: Simplified configuration tool 

• 0 882 30: Advanced configuration tool

When the sensor receives an IR command via a configuration tool, 

it emits a beep confirming that the modification has been taken into 

account.

For more information about setting parameters, refer to the data sheet 

for the configuration tool Cat. No. 0 882 30.

-  Return to factory settings:

1

st

 press: Short press on LEARN: the LED flashes slowly.

2

nd

 press:  Press and hold down LEARN for 10 seconds until the LED 

flashes quickly.

Sensor parameters

Default 

value

Modifiable  

parameters

Configuration  

tools

0 882 30 0 882 35

Light level threshold

150 lux

20, 100, 300, 500, 

1000 lux

0 - 1275 lux

A

dv

anc

ed 

mo

de

Calibration

0 - 99995 lux

Regulation

Active

Activate/

Deactivate

Light 

contribution

Auto

Auto - 1275 lux

Summary of Contents for 0 488 17

Page 1: ...re 20 C to 70 C 2 TECHNICAL CHARACTERISTICS continued Cover removed CONTENTS Page 1 Use 1 2 Technical characteristics 1 3 Dimensions 2 4 Connection 2 5 Installation 4 6 Removal 4 7 Operation 5 8 Settings 6 9 Performance 7 10 Care 7 11 Standards and approvals 7 12 Troubleshooting 7 230 V 2000 W 8 5 A 1000 VA 4 3 A 10x 2x36 W 4 3 A 500 VA 2 1 A 1000 VA 4 3 A 500 VA 2 1 A I max 2A 110 V 1000 W 500 VA...

Page 2: ...3 DIMENSIONS Without protective cover 4 CONNECTION Number of terminals 4 Type of terminals automatic Terminal capacity 2 x 2 5 mm2 Stripping length 8 mm 4 1 Wiring with auxiliary control 4 2 Wiring without auxiliary control Auto on Auto off Wiring 65 93 Ø 1 2 2 50 73 Ø 1 2 2 52 With protective cover 100 m max 8 5 A max 8 5 A max 36 56 ...

Page 3: ... 17 10 2017 Created 04 10 2012 Catalogue number s 0 488 17 Corridor sensor PIR 4 CONNECTION continued 4 3 Wiring for several loads connected in parallel 4 4 Wiring for a single load connected in parallel 100 m max L1 PB L2 LN S1 S2 SN PB L S1 S2 SN 100 m max ...

Page 4: ... Technical data sheet S000072383EN 2 Updated 17 10 2017 Created 04 10 2012 Catalogue number s 0 488 17 Corridor sensor PIR 5 INSTALLATION 6 REMOVAL 1 2 3 1 2 50 Ø 68 Ø 68 Ø 65 Ø 65 Ø 120 Ø 120 0 488 75 0 3 to 20 mm ...

Page 5: ...the end of the time delay or when the light level threshold has been reached Auto ON OFF mode The load will be switched on and off automatically Option It is possible to control the sensor by infrared remote control using Cat Nos 0 882 00 01 20 31 32 33 7 1 More than one sensor and more than one load L1 OFF L2 OFF Ln OFF S1 OFF S2 OFF Sn OFF 1 s L1 ON L2 ON Ln ON S1 ON S2 ON Sn ON L1 ON L2 ON Ln O...

Page 6: ...via a manual switch 8 SETTINGS continued 8 1 Detection parameters continued Detection system Initial detection The load is switched on as soon as the first detection occurs if the natural light level is below the light level threshold Maintain The load remains active if another presence is detected Restart In manual mode After switch off any new detection within a 30 second period triggers an auto...

Page 7: ...us Substances Decrees and or regulations Public buildings Workplace buildings High rise buildings PROBLEM CAUSES SOLUTIONS Lighting stays on when there is no one present Some sources of interference such as air currents vibrations and radiators can cause unintended operation 1 Reduce the sensitivity level 2 If the interference continues using the configuration tool go into the Detection system par...

Reviews: