INSTRUCTIONS FOR SELF-DIAGNOSTIC TEST:

Once the unit is properly installed according to the installation instruction sheet and AC power supplied, 
the dual color LED indicator will come ON and the self-diagnostic test function will automatically initiate. 
The LED indicates the unit’s status. A STEADY GREEN LED indicates normal service; FLASHING 
GREEN indicates the unit is testing; GREEN/RED FLASHING indicates the battery is charging; RED (in
different combinations) would indicate a service alert. Refer to the SERVICE INDICATION chart below for
more details. The LED would be OFF when the unit is in emergency mode.      

 

 

 

 

SELF-DIAGNOSTIC SERVICE

 

The self-diagnostic function is factory preset and performs the following:
a. Monitoring of battery, battery charger, and lamps (both local and remote lamps when applicable )
b. Self-testing and a 30-second or longer discharge once every 30 days, after AC power has been

supplied for a minimum of 24 hrs.

c. Self-testing and a 30-minute  or longer discharge once every 180 days, after AC power has been

supplied for a minimum of 24 hrs.

d. Self-testing and a 90-minute discharge once every 365 days, after AC power has been supplied for

a minimum of 24 hrs.

 

 

 

 

 

 

 

SERVICE INDICATION

 

MANUAL TESTING

 

 

WARNING:

The unit also provides for manual testing by pushing the test button in a specific pattern. 

 

Action 

Reaction & LED Indication 

Push test button Once (within 2 seconds) 

30-second test: FLASHING Green

Push test button Twice (within 2 seconds) 

30-minute test: Green FLASHING twice

Push test button Three times (within 2 
seconds) 

90-minute test: Green FLASHING three times

Push test button and hold for 3 seconds (In 
test mode) 

Cancels test. If self-test is cancelled it is recommended that a 
manual test of the same duration be performed at a more 
convenient time to ensure compliance

Push test button and hold for 6 seconds (In 
test mode) 

System reset

 

 

 

a) Make sure that power is OFF before making any electrical connections.
b) Unused wires must be capped using enclosed wire nuts.

 

 

LED Indicator 

Status 

One flash red 

Replace electronics 

Two flash red 

Replace battery 

 

Four flash red

 

Replace lamp head board

 

 

Five flash red

Replace Remote lamp head 

or R

emote lamp head disconnected

 

Steady red

 

Battery disconnected

Solid green

 

Trickle charge

Flashing green

 

In test

 

Red/Green flashing

Hi charge