background image

1

3

2

4

1.

4.

HOT WATER CONNECTIONS

sound insulation

mat, 30 mm (1")

fl oor hatch

heating unit

cover

electrical connections

heating insert

heating unit box

hole for water pipe return

hole for water pipe inlet

If 1 - 3 thermostats are used,  or if more than one thermostat 

is installed in the same room, install a jumper between the 

connection blocks 3, 6, 9 and 12 as required.

Refer to the fl oor plan for thermostat locations.

ELECTRICAL CONNECTIONS

Install the heating unit boxes in the correct location, with the height 

adjusted so that the lid is fl ush with the concrete surface, before pouring 

the concrete.  Refer to the instructions on the box cover.
1.  Run conduit from one of the cable inlets on the box to the local 

disconnect for 230V power. Run conduits from the remaining cable 

inlets to a convenient location above the slab for each of the 24V 

thermostats and optional signal wiring to the boiler.

2.  Connect the sleeves for the inlet and outlet water pipes to the 

water pipe connections of the furnace box. Install the water pipes, 

and make sure they extend at least 100 mm (4") into the box.

3.  After  the  concrete  has  dried  suffi ciently  with  the  construction 

heater, prepare the box for the heating unit according to the steps 

below, which are to be performed by an authorized electrician and 

plumber.

4.  Clean the furnace box carefully. No water or dampness should be 

in the box or pipe system when installing the permanent insert.

ASSEMBLY

1.  Check the electrical data on the unit so that 

other installation materials are compatible. 

The installation must be performed by an 

authorized electrician.

2.  Install  a  properly  sized  two-pole  local 

disconnect  to  enable  total  isolation  for 

servicing.  GFI protection is required.

3.  Use  properly  sized  copper  wire  for 

connection to the panel.

4.  Connect thermostats and verify that each 

zone responds to the correct thermostat.

5.  Seal  the  conduits  which  run  into  the  unit 

using a duct sealing compound for both water 

and electrical, after the water and electrical 

connections  have  been  made,  for  sound 

attenuation.

6.  Install  the  heating  unit  cover.  Test  run 

for 1 hour and then open for a check.  If 

necessary clean, check for dryness, and 

test run again.  If moisture is still present, 

re-install construction heater and run until 

the system is dry.

7.  Install the sound insulating foam-rubber 

mat between the heating unit cover and 

the fl oor hatch. 

8.  Install  the  fl oor  hatch.    If  desired,  use 

standard transition trim between the hatch 

and the fl oor. 

1.  Flush  debris  and  bleed  air  from  both  lines  before  connecting 

insert.

2.  Install  'swivel  faucet  adaptors'  (female  threaded  adaptors  with 

integral gasket for ½” lavatory-style straight threaded NPSM male 

fi ttings) on PEX water pipe, and adjust pipe position so that the 

end of the fi ttings stick 38 mm (1.5") inside the box (Picture 1).  If 

PEX pipe is not used, or a 'swivel faucet adaptor' is not available 

for the PEX pipe used, please contact Legalett for assistance.

3.  Disconnect the two vertical pipes from their top elbow connections, 

which are loosely mounted on the heating unit inlet and outlet pipes. 

Connect lower

 

elbow connections to the water pipes (Picture 2).

4.  Install the heating insert so that the vertical pipes stick into the top 

elbow connections above and tighten the joints (Pictures 3 and 4).

5.  Turn on water and check for leaks.

6.  Once the electrical connections have been completed, turn up all 

thermostats to open all the valves and then bleed any air from the 

heating insert using the bleed screws on the exchangers.

water pipe

connections

electrical 

connections

4000W-24

heating unit box 

4000A 50/50 (2")

Heating unit box 

4000A 100/100 (4") 

is similar

www.LEGALETT.com

2.

3.

24

L1

L2

1

2

3

4

5

6

7

8

9

10

11

12

B

la

ck

Br

o

w

n

B

lu

e

Valve 1

Fan

1

M

400mA

Valve 2

Valve 3

Valve 4

230V
60Hz

15A

C

R

C

W

Thermostat 1

R C

W

R

C

W

Thermostat 2

R C

W

R

C

W

Thermostat 3

R C W

R

C

W

Thermostat 4

R C

W

24V

230V

30º C (86º F)

38 mm (1.5") to fi tting gasket

Reviews: