FAULT MESSAGES
FAULT
DESCRIPTION
POSSIBLE CAUSES
EXTERNAL
External fault: TB-13D is open or closed
Check setting of Parameter
to TB-2, depending on setting of
50-TB13D.
Parameter 50 - TB13D.
Check devices wired between
TB13D and TB-2.
DB ERROR
Dynamic Brake fault: DB circuit has
The DB duty cycle is too high,
sensed a resistor overload.
causing the resistors to overheat.
CONTROL
Control Board fault: New software has
Perform a factory reset using
been installed that is different from the
Parameter 65-PROGRAM.
previous version.
This will update the software
and allow the fault to be reset.
INTERNAL
Internal Fault: The microprocessor
Electrical noise on control
INTERN (#)
has sensed a problem.
wiring.
Defective microprocessor.
Blank Display
The power supply has shut down.
Check heatsink fans (if equipped).
(drive will not run)
This can be the result of clogged or
Clear any obstructions. If they
failed heatsink fans.
are not clogged, contact the AC
Tech Service Department.