background image

 

 

merchandiser. On outdoor cabinet models, the melt 
water will exit the drain tube directly to the ground.   
On indoor cabinet models, the consumer needs to 
install the condensate evaporator heater assembly 
(described in the 

Installation

 section of this 

manual) onto the exterior back wall of the cabinet.  
The melt water from the defrost cycle will drain 
into a catch pan where it will then be heated to the 
point of evaporation. The function of the condensate 
evaporator’s heat element should be checked 
routinely. Failure of the element could result in an 
over-flow condition for the assembly’s drain pan.  
A simple check of the heater would be a touch test 
of the surface temperature of the assembly’s 

housing. The condensate evaporator’s heat element 
is energized continuously so the surface of the 
housing should always be hot to the touch. If testing 
the heat element with a meter, the element can be 
unplugged from its’ power source and a resistance 
reading can be taken through the plug’s bladed 
terminals. The condensate heater is rated to generate 
125 watts of power, which translates to 
approximately 106 ohms of resistance. 
 
It is recommended to check the operation and 
condition of the evaporator coil and for signs of 
excessive ice buildup every 3 months 
 

Auto-Defrost Electronic Control:

 The AD 

freezer comes equipped with an electronic control 
(as described in the OPERATION section of this 
manual). The timer is factory set for a 24 minute 
defrost cycle to occur at 4-hour intervals. Like a 
mechanical timer, the electronic control will switch 
power from run mode (condensing unit and 
evaporator fans) to defrost mode (defrost heat 
element). Whereas the mechanical timer operates 
strictly on a timed cycle, the duration of the 
electronic control’s defrost cycle is controlled by 
the temperature at the sensor probe “P2.” If the 
temperature at this probe reaches 60° prior to the 
24-minute timed cycle ending, the control will 
override the timed cycle and immediately switch 
power from the defrost mode to the run mode. If 
temperature is not reached at probe “P2,” the 
defrost cycle will continue for the entire 24-minute 
programmed cycle prior to returning to run mode. 
Energizing the defrost circuit in the electronic 
control can be verified with the illumination of the 
“melting snowflake” and the letters “DE” appearing 
on the control’s display screen.  
 
The electronic defrost circuit is equipped with a 
defrost termination safety switch and is attached to 
one of the evaporator coil tubes (located inside the 
Unit Cooler Assembly). This switch senses 
temperature and will cut power to the defrost heat 
element should the temperature at the surface of the 
switch reach 100° F. This switch only terminates 
power to the heat element and will not end the 
timed / temperature defrost cycle. Once the 
merchandiser has returned to run mode, the 

termination safety switch will re-set when the 
temperature at its’ surface reaches 70° F. 
 

Warning!

 The defrost termination / safety switch 

functions as a possible fire protection device. Do 
not remove or by-pass the switch from the defrost 
circuit. 
 

Note: 

If an electronic control AD unit loses power, 

it will automatically enter a defrost cycle.  
 

Note:

 Certain models may contain a drain line 

heater to prevent ice from forming inside the drain 
tube.  
 

Solid Door Models and Maintenance:

 

Cabinets designed for outdoor use will have a metal 
clad door that has been insulated with the same 
urethane foam insulation as the cabinet. For routine 
cleaning of the door’s exterior surface, a mild 
detergent diluted in warm water should be adequate.   
Routine inspection of the door gasket seal is 
recommended. If damage has occurred, replace the 
gasket. 
 

Hinge Spring Tension:

 A simple test of the 

spring-load tension is to open the door just enough 
to insert two fingers between the surface of the 
cabinet and the handle side of the door. When the 
fingers are withdrawn, there should be enough 
tension set on the hinge spring-loads to slowly 
move the door to a closed position. If the door does 
not move from this two-finger location, it’s likely 
that either the spring-load requires re-tensioning or 

Summary of Contents for REACH-IN STORAGE Series

Page 1: ...950 1 800 766 5337 www leerinc com STORAGE FREEZER INSTALLATION OPERATION AND SERVICE MANUAL WARNING This product can expose you to chemicals including nickel which is known to the State of California...

Page 2: ...de Display 4 Electronic Control Operation 5 Auto Defrost Control 5 Possible Displayed Alarm Codes 5 Loading Product 5 Condenser Fan Pressure Switch 6 Maintenance 6 Cleaning the Freezer 6 Cleaning Door...

Page 3: ...ls is available Contact the Merchandiser Sales Department at Leer Inc for additional information Electrical Warning Component parts shall only be replaced with like components Electrical and servicing...

Page 4: ...ack surface of the condensate evaporator housing and any wall surface behind the cabinet which allows for heat dissipation away from the surface of the wall The main power cord should also be routed t...

Page 5: ...e Possible Displayed Alarm Codes P1 Air Probe failure The control will override the P1 functions and cycle the compressor for 17 minutes until the probe fault can be corrected P2 Evaporator Probe fail...

Page 6: ...like material that can be cleaned using most kitchen and bath cleaners designed for mildew removal Review manufacturer information and instructions on any cleaning agent prior to use to determine the...

Page 7: ...d immediately switch power from the defrost mode to the run mode If temperature is not reached at probe P2 the defrost cycle will continue for the entire 24 minute programmed cycle prior to returning...

Page 8: ...unting screws should hinge adjustment be required See Figure 2 for instruction regarding spring load installation and adjustment SPRING CARTRIDGE INSTALLATION INSTRUCTIONS Figure 1 Figure 2 Figure 3 1...

Page 9: ...ng tension Figure 2 Spring Install Instructions Solid Door Magnetic Gasket Replacement Instructions 1 Position solid door on a flat non abrasive surface exterior side down 2 Remove old gasket by grasp...

Page 10: ...10 Step 5 Figure 3 Door Gasket Install...

Page 11: ...11 Electronic Control AD Wiring Diagram W Relay...

Page 12: ..._____________ __________________________________________________________________________________________ __________________________________________________________________________________________ ____...

Page 13: ...the original buyer user In event of any claim for breach of express warranty Seller shall be responsible for labor charges for repair or replacement of any defective part s or assembly only for defec...

Page 14: ...14 MODEL NO ______________________ SERIAL NO ______________________...

Reviews: