Parameter Setting
ATSC 702
27
5.4
、
Timer
Menu:
No.
Option
Definition
Default
Adjustment Range
4.1
1FT
Source I Failure Timer
5S
0-60S
4.2
1RT
Source I Return Timer
2Min
0-60Min
4.3
Ⅰ
→
Ⅱ
0DT
Source I to Source II dead time in 0
position
0S
0-20S
4.4
2FT
Source II Failure Timer
5S
0-60S
4.5
2RT
Source II Return Timer
2.0 Min
0-60.0Min
4.6
Ⅱ
→
Ⅰ
0DT
Source II to Source I dead time in 0
position
0S
0-20S
4.7
CT
Generator cool down Timer
5Min
0-60Min
5.5、Close transfer
序号
选项
说明
默认值
范围
5.1
Close transfer
enable in manu
Turn on or off closed transition under
manual mode
OFF
OFF/ON
5.2
Close transfer
enable in auto
Turn on or off closed transition under
automatic mode
OFF
OFF/ON
5.2
Max Volt Delta
Maximum voltage difference between
the two sources to be synchronised
10V
5‐50V
5.3
Max Freq Delta
Maximum frequency difference
between the two sources to be
synchronised
1Hz
0‐10Hz
5.4
Max phi Delta
Maximum phase angle difference
between the two sources to be
synchronised
2'
2‐20'
5.5
Max sync time
Maximum waiting time for
synchronization conditions,After this
time,an alarm is performed.
6S
0‐1000S
5.6
Sync hold time
Instantaneous parallel time in closed
transition
0.30S
0.01‐1.00S
5.7
Sync over time
Enforce break time in closed transition
0.00S
0.00‐600.00S
5.1 Turn on closed transition function in manual mode; you need to set the OFF POSITION to "two‐position" to perform closed transition. When the
power source mode set as mains to mains,if S1&S2 power parameter difference meet 5.2 Max Volt Delta 5.3 Max Freq Delta5.4 Max phi Delta in counting
time, then it will implement transfer synchronized, The Instantaneous parallel time is based on 5.6 "sync hold time". During operation If the waiting
time over 5.5 max sync time it will perform alarm: closed transition overtime,if power source type set as” mains‐genset” the controller start the generator
output first, and S1&S2 will transfer synchronized when meet the closed transitions conditions, if the waiting time over max sync time it will perform
alarm.
5.2 Turn on closed transition function in auto mode: need to operate under return to “main power”, if the waiting time over max sync time it will remind
closed transition overtime.
Summary of Contents for ATSC702
Page 1: ...ATSC702 ATSC702 ATSE Controller Operation Manual...
Page 4: ...ATSC 702 3 I I II II 0 0 3S 3S 3S 3S 3S...
Page 5: ...ATSC 702 4 3S S1 S2 3S ESC I II O 3S language ESC...
Page 12: ...ATSC 702 11 1 1 I I II II Load 2 7 2 380V 3 220V 4 0 120 240 5 A01 A01 6 A21 A21 7 2...
Page 14: ...ATSC 702 13 14 1 2 2 3 4 1 15 S1 S2...
Page 17: ...ATSC 702 16 6 2...
Page 36: ...Mechanical dimension and panel opening ATSC 702 35 6 2 Typical application...