![LEDone LOD-EXTED-M20W Series Installation Manual Download Page 2](http://html1.mh-extra.com/html/ledone/lod-exted-m20w-series/lod-exted-m20w-series_installation-manual_1867686002.webp)
Phone:
(844) LEDONE6 |
Fax:
1-510-217-9461 |
Web:
www.ledonecorp.com
`
WIRING DIAGRAM:
•
Do NOT mate connector until installation is completed and the AC power is supplied.
•
Test the accessory leads-observe proper polarity wiring.
OPERATION:
•
AC Operation: AC power is present. The AC driver operates the LED load as designed. The AC LED driver that has an
output current is not to exceed 4.0 A. The emergency pack is charging in a standby mode. The charging indicator will
light up showing that the battery is charging.
•
Emergency Operation: When the AC power goes out, the emergency pack detects the power outage and
automatically switches to the emergency mode. The charging indicator will turn off. The LED load is illuminated for a
minimum of 90 minutes. When the AC power is restored, the emergency pack will switch back to Normal Mode and
start to re-charge again.
•
Malfunction Mode: The green LED will light up when the emergency driver is normal and without any internal circuit
fault. When the battery is disconnected, the emergency driver circuit is faulty, and the green light will turn off.
LOD-EXTED-M20W Series Installation Guide
NOTE:
•
When the dial switch code 1 and 2 turn off, the emergency
power is 20W.
•
When 1 is turned off and 2 is turned on, the emergency
power is 15W.
•
When 1 is turned on and 2 is turned off, the emergency
power is 10W.