If the installation is not in hazardous area (safety barriers are not used):
The cable should be a simple cable used for power purposes, for example 3 times 1 or 1.5 mm².
Do not use a communication cable with twisted wires or a coaxial type.
If the installation is in hazardous area
(safety barriers are used):
Use a cable of 3 conductors (gauge as described above), non-twisted inside outer jacket
(communication cables are not good).
The jacket should withstand 500 V RMS.
The capacitance between each two wires should not exceed 200 pF/meter.
The inductance of each wire should not exceed 0.7 uH/meter.
Select such a cable from a catalog or test its capacitance and inductance.
A shielded cable is not required in most cases.
Zener Safety Barriers for installation in hazardous area:
Note:
MTL 715+ and 710+ are obsolete. Use MTL 7715+ and 7710+.
Summary of Contents for ID-220 SERIES
Page 2: ...SLC 220 User Guide Rev 2 0 June 2018 2...
Page 4: ...SLC 220 User Guide Rev 2 0 June 2018 4...
Page 6: ...SLC 220 User Guide Rev 2 0 June 2018 6...
Page 12: ...SLC 220 User Guide Rev 2 0 June 2018 12...
Page 36: ...SLC 220 User Guide Rev 2 0 June 2018 36...
Page 64: ...SLC 220 User Guide Rev 2 0 June 2018 64 Setting a User through the LCD...
Page 70: ...SLC 220 User Guide Rev 2 0 June 2018 70...
Page 71: ...SLC 220 User Guide Rev 2 0 June 2018 71 9 Appendix A Installation in Hazardous Area...
Page 72: ...SLC 220 User Guide Rev 2 0 June 2018 72...
Page 78: ...SLC 220 User Guide Rev 2 0 June 2018 78...
Page 82: ...SLC 220 User Guide Rev 2 0 June 2018 82 13 Appendix E SLC 220 Drawings...
Page 83: ...SLC 220 User Guide Rev 2 0 June 2018 83...