1a Closer is handed at factory and must match hand of
door. hand of closer shown on mounting channel.
Voltage shown on SENTRONIC cover plate must
match voltage supplied to door frame.
1b If door & frame are not prepared for closer & track
then prepare in accordance with details on opposite
side.
1c
Remove cover plate from track. Assemble flexible
conduit connector to tapped hole provided in top of
track. Connect power supply wires to track terminal
strip. See wiring diagram below. Insert track roller
into track. Make sure roller stud is inserted into hole
in track slide. Insert track into frame and secure with
proper screws as shown on opposite side. Replace
cover plate.
1d Insert closer in cut out in door & secure with proper
screws.
1e Place arm on closer shaft and secure with shaft screw.
1f Loosen set screw in end of arm, open door part way
(about 30°), pull arm away from top of door and
connect to track roller. Tighten set screw firmly. Open
door to hold open position.
Backcheck
Main
Speed
Latch
Speed
Backcheck
Main Speed
Latch Speed
Door
Closer
Shaft Screw
Arm
Set Screw
Cover
Plate
Track
Optional Concealed Flexible
1/2” Conduit Or 12V Or 24V
Concealed Wiring
To Either Terminal
To Either Terminal
Optional Switch
Input Voltage
12V AC/DC
24V AC/DC
or
115V AC/DC
(Usually from
alarm panel
or detector)
Polarity Not Important
Roller
End Cap
Regulation
L
Important
Do not allow door to slam into frame. A “normal” closing time
from 90° open position is 5 to 7 seconds, evenly divided between
main swing speed and latch swing speed. Use socket screw key
furnished. To slow
MAIN SPEED
of door, turn regulating screw
(nearest arm) clockwise. To slow
LATCH SPEED
of door, turn
regulating screw (nearest hinge) clockwise.
Backcheck
To increase
BACKCHECK
, turn regulating screw (nearest latch)
clockwise. Use lightest
BACKCHECK
that will retard door opening
sufficiently.
DO NOT ABRUPT BACKCHECK NOR EXPECT DOOR CLOSER
TO ACT AS A STOP
CAUTION
Improperly installed or regulated closers can cause
property damage or personal injury. Please follow these
instructions carefully.
Backcheck
Main
Speed
Latch
Speed
Backcheck
Main Speed
Latch Speed
Door
Closer
Shaft Screw
Arm
Set Screw
Cover
Plate
Track
Optional Concealed Flexible
1/2” Conduit Or 12V Or 24V
Concealed Wiring
To Either Terminal
To Either Terminal
Optional Switch
Input Voltage
12V AC/DC
24V AC/DC
or
115V AC/DC
(Usually from
alarm panel
or detector)
Polarity Not Important
Roller
End Cap
Electrical Checkout
1. With power on, open door fully. Door should remain in open
position. If door does not stay open check electrical input.
2. Turn power off. Door should close immediately. Turn power on
and leave door in the open position.
3. System should be checked at frequent intervals. It is
suggested that steps 1 & 2 be repeated every 90 days.
L
Note: If door does not close when power is off, consult
LCN Representative or factory.
Backcheck
Main
Speed
Latch
Speed
Backcheck
Main Speed
Latch Speed
Door
Closer
Shaft Screw
Arm
Set Screw
Cover
Plate
Track
Optional Concealed Flexible
1/2” Conduit Or 12V Or 24V
Concealed Wiring
To Either Terminal
To Either Terminal
Optional Switch
Input Voltage
12V AC/DC
24V AC/DC
or
115V AC/DC
(Usually from
alarm panel
or detector)
Polarity Not Important
Roller
End Cap
L
NOTE: Not for installation on Ul rated 20 minute wood core doors per can/ulc-s104-10
3130-SEL Sentronic