12
02-5:Battery quantity(PCS)
LCDDisplay
Setting
When EP is set to ON,the
PCS
option appearson the function
setting page,will enter the passwordpage,enter the password
(the general passwordis 135),you can set the number of
batteries. Thedefault battery numberis 16pcs,whichcan be set
to 16/18/20pcs.
02-6:ChargerCurrent(CHG)
LCDDisplay
Setting
When EP is set to ON,the
CHG
option appearson the functional
setting page, the chargingcurrent can be set, 1-12Aoptional,
default 1A.Noted: if UPS built-inbatteries, the charger current
default 1A, andcant be changed.
02-7:Input Neutral and Livecable reverse alarm function
LCDDisplay
Setting
The input neutral and live cable reverse alarm mode is closedby
default, can chooseto open to improve the safety of the system.
Note: Factory settingsdefault closed, pleaseopen if youneed.