The actual point of alarm is the sum of the set 
point and the "high alarm".  The system will re-
turn to normal when the temperature reaches the 
sum of the set point and the "high alarm" minus 
the hysteresis.

Parameter Programming

Set Point (SP) is the only parameter the user 
can access without code protection

• Press 

SET

.  

SP

 Text will appear on the display

• Press 

SET

 again.  The real value is shown on the 

display.

•  The value can be modified with the 

UP

 and 

DOWN

 

arrows.

• Press 

SET

 to enter any new values.

• Press 

SET

 and 

DOWN

 at the same time to quit 

programming or wait one minute and the display 
will automatically exit programming mode.

The keyboard code can be reset to ZERO by 
turning off the controller and turning it on again 
while keeping the SET key depressed.

Access to all code protected parameters.

• 

Press 

SET

 for 8 seconds.  The access code value 

00 is shown on the display. (Unit comes with code 
set at 00 from factory).

•  With the 

UP

 and 

DOWN

 arrows, code can be set 

to user needs.

• Press 

SET

 to enter the code.  If code is correct, the 

first parameter label is shown on the display (

SP

).

•  Move to the desired parameter with the 

UP

 and 

DOWN

 arrows.

• Press 

SET

 to view the value on the display.

•  The value can be modified with the 

UP

 and 

DOWN

 

arrows.

• Press 

SET

 to enter the value and exit to text pa-

rameter.

•  Repeat until all necessary parameters are modified.
• Press 

SET

 and 

DOWN

 at the same time to quit 

programming or wait one minute and the display 
will automatically exit programming mode.

Display Messages

In normal operation, the probe temperature will be 
shown on the display.  In case of alarm or error, the 
following messages will be shown: The alarm LED 
indicates and active alarm, it will flash if an alarm is 
cleared but alarm condition still exists.

• 

ALH

 = High Temp Alarm

• 

ALL

 = Low Temp Alarm

• 

Er

 = Memory Error

• 

--

  = Short-Circuit Probe Error

• 

oo

 = Open Probe Error

Alarm can be cleared by pressing the 

DOWN

 button. 

The alarm LED will flash while alarm condition per-
sists but the alarm message will not be shown.

Warning:

 This product contains chemicals known to the 

State of California to cause cancer and birth defects or 

other reproductive harm.

(Installer: California law requires that this warning be 

given to the consumer.)
For more information: www.oehha.org/prop65

GUARANTEE

We guarantee the Lawler Mixing Valve to be free from 

defects in workmanship and material, and for a pe-

riod of one year from date of purchase, will replace 

any parts found by us to be defective. We will not be 

held responsible, however, for any labor incidental 

to, or for any damages caused by defective mate-

rial. Each mixing valve is thoroughly inspected and 

tested under actual conditions at our factory.

Reviews: