background image

temperedwater.com

5330 East 25th St.

Indianapolis, IN 46218
Phone (317) 261-1212

Fax (317) 261-1208

INSTALLATION &

MAINTENANCE MANUAL

Design and specifications subject to change without notice.

Please refer to 

temperedwater.com

 to ensure most

current data sheet and other design solutions. 

CAUTION: When maintaining and adjusting the 

mixing valve, all fixtures should be isolated from 

use. Lawler Manufacturing Co., Inc. recommends 

that you work safely at all times and in a manner 

consistent with the OSHA Lock/Tagout standard,  

29 CFR 1910.147 and other applicable standards.

temperedwater.com/patents

M 66 E

ASSE 1017 Approved
ASSE Lead Free Certified

Certified to CSA B125.3

NOTICE!

 

No mixing valve will work satisfactorily if improperly installed. We suggest, therefore, that you read 

these instructions carefully before installing and follow directions as outlined. Handle the mixing valve with care.

Series 66

Thermostatic Water 

Controller

This installation & maintenance manual covers all 

configurations of the Series 66.

DIMENSIONS

  Valve Number 

A  N.P.T. 

B  N.P.T. 

C

 

66-25

 

3/4” 3/4”  10”

 

66-50

 

3/4” 1”  10”

 

66-80

 

1”  1-1/4” 11”

 

66-125*

 

1-1/4”  1-1/2” 12-3/4”

 

66-150*

 

1-1/2”  2” 13-1/4”

 

66-200*

 

2”  2” 15”

Dimensions are for reference purposes only. For rough-in dimensions 
please refer to Lawler’s Revit/BIM models found at temperedwater.com.

*66-125, 66-150 and 66-200 are not lead free certified

71762_66.pdf

B

A

A

C

CAPACITIES – GPM SERIES 66

 Pressure Drop PSI 

10 

20 

30 

45 

60 

Min. 

 

 

 

 

 

 

 

 

Flow 

 

 

 

 

 

 

 

 

GPM

  Valve Number 

 

 Capacity – GPM

 

66-25

 

9  12 17 21 25 28  4

 

66-50

 

18 25 34 41 50 57  8

 

66-80

 

28 

39 

54 

66 

80 

91 

12

 

66-125*

 

43 

60 

85 

103 

125 

144 

19

 

66-150*

 

52  72  100 124 150 174  23

 

66-200*

 

64 

96 

133 

165 

200 

230 

30

1/2 gpm when properly installed in recirculated system.

CAPACITIES – LPM SERIES 66

 Pressure Drop PSI 

10 

20 

30 

45 

60 

Min. 

 

 

 

 

 

 

 

 

Flow 

 

 

 

 

 

 

 

 

LPM

  Valve Number 

 

 Capacity – LPM

 

66-25

 

34 

45 

64 

79 

94 

106 

15

 

66-50

 

68 

95 

129 

155 

189 

216 

30

 

66-80

 

106 

148 

204 

250 

303 

344 

45

 

66-125*

 

163 

227 

322 

390 

473 

545 

72

 

66-150*

 

197 

273 

379 

469 

568 

659 

87

 

66-200*

 

242 

363 

503 

625 

757 

871 

114

*66-125, 66-150 and 66-200 are not lead free certified