REFERENCE 

MARKS

THERMOSTAT

 

(2)

Temperature Adjustment

Valves are normally factory set for a maximum 110°F 

outlet temperature, or that stamped on the label. If it 

is desired to change this setting, proceed as follows:

While allowing water to flow through the controller:

1.  Remove screw #1.

2.  With  a 

5

/

32

  allen  key,  turn  adjusting  screw  #2 

counterclockwise  to  increase  temperature  or 

clockwise to decrease temperature.

3.  When temperature is correct, replace screw #1.

Note:

 If outlet temperature desired is 15°F or more 

higher than that stamped on the label, contact 

the factory or a representative for a special 

thermostat.

Figure B

1. Place a 

3

/

8

 wooden dowel 

rod into center of thermo-

stat  then  place  in  85°F 

water.  Make  a  reference 

mark on the rod as shown 

in fig. A.

2. Now insert thermostat into 

hot  water  that  is  at  least 

20°F  higher  than  the  set 

temperature  stamped  on 

label.

3. The rod should move out 

of the thermostat approxi-

mately 

1

/

8

. If the rod shows 

no  movement  or  can  be 

pushed inward, a new ther- 

mostat is required.

Checking Cold Water Shut-Off (Cont.)

b. Spring #13 has lost its strength and should 

be replaced.

Note:

 Lack of water flow can be normal on the first 

test  if  the  temperature  of  the  cold  water  is 

below  75°F.  A  quick  test  is  to  momentarily 

turn on the hot water to warm the thermostat. 

If  flow  then  starts,  the  thermostat  is  good; 

failure  to  obtain  flow  when  first  starting,  or 

when valve is cold, is a normal reaction.

Checking Hot Water Shut-Off

Allow  full  hot  and  cold  water  to  flow  through  the 

valve for one minute. Shut off the cold water stop 

and  check  valve  only.  The  hot  water  should  be 

reduced to a negligible amount.
Failure to do so will indicate:

a. The hot water supply is not 20°F above the 

required maximum temperature setting.

b. The plunger is sticking and requires cleaning 

or replacement.

Inspection and Cleaning Valve

Shut  off  the  hot  and  cold  water  supply  to  the 

controller. Remove bonnet #19. To replace pusher  

O-ring  #18,  remove  pusher  #21  from  bonnet  #19 

and replace O-ring. Reassemble in reverse order.
With  the  bonnet  assembly  off  the  valve,  remove 

thermostat  #22  and  check  and  clean  (see  fig.  A). 

Unscrew bottom plug #14 and remove valve spring 

#13  and  plunger  #12  (see  fig.  C).  If  the  assembly 

does  not  slide  out,  remove  the  plunger  with  liner 

#11  and  gently  tap  plunger  until  it  becomes  free. 

Clean and polish the liner and plunger with very fine 

emery cloth until plunger moves freely in the liner.
With the liner out of the valve, replace liner O-ring #10.

Note:

 If the piston or liner is nicked or shows signs 

of excessive wear, it should be replaced.

Caution:

 The liner and plunger cannot be dropped. 

Please handle carefully. The liner must be inserted 

correctly.  Carefully  examining  the  outside  of  the 

liner will reveal a very small difference in diameter 

between the upper half and the lower half. On reas-

sembly, the smaller diameter must be inserted first 

through bottom plug opening. 

Figure A

1

19

2

18

21

Warning:

 This product contains chemicals known to the 

State of California to cause cancer and birth defects or 

other reproductive harm.

(Installer:  California  law  requires  that  this  warning  be 

given to the consumer.)
For more information: www.oehha.org/prop65