Attention!  Any  assembly  work  on  the  ventilation  unit  may  only  be  carried  out  with  the  mains 
voltage  disconnected!  Additional  installations  and  electrical  components  in  this  ventilation 
system are not admissible!! 

3 Installation - Fan Insert, Control Board and Decor Screen 

3.1  

If necessary, remove the plaster protection cap from the housing.  

 

If necessary, check the electrical connection and the position of the mains supply terminal (A). 

 

3.2  

Snap the fan insert firmly into place and screw on the mains connection area (B). 

 

 

3.3  

Fasten the control board (E) in the provided mounting space of the grille frame (D). 

 

3.4  

Connecting the control board to the fan insert.  

 

Ensure that the ribbon cable is routed properly. 

 

3.5 

Clear the screw openings according to the housing used (UP, Ap, KL). 

 

If necessary, clear the screw openings. Fasten the grille frame (D) to the fan housing using 

 

the screws supplied. Insert Filter. Put on front cover (G) and snap it into place. 

 

Attention: The grille frame is always mounted according to the mounting position of the fan! 
The front cover can then be mounted on the grille frame in two optional positions rotated by 

180°!  

 

3.6  

With two-room fans: Insert the screen (Q) under the filter in the grille frame. (The screen for 
two-room fans is included in the two-room accessories) 

3 Installation - Additional modules

 

 

One of the optionally available additional modules (5/BM (40082), a motion detector module with 
radar sensor or FM-EO (40083), a radio module for communication with other fans or a Smart Home 
System) can be plugged in to expand the functionality.To do this, proceed as follows: 
 

3.7 

Detach the control board (E)  from the grill frame (D). Plug the additional module into the 6-

 

pin connector under the control board as shown in the illustration. Fasten the control board 

 

again in the grill frame according to step 3.3. 

 

3.8 

The vertical and horizontal detection range of the motion detector module is 90°. 

 

Note: After applying the mains voltage to the completed ventilation unit, the LED on the 

control board flashes once. 

16  

 

Note: 

A variety of Silvento ec ventilation functions can be created using the DIP switches integrated 

in the control board of this type and via optional add-on modules. 

Additional installations and electrical components in the ventilation unit are not permitted! 
Connection diagrams for further fan functions available on request

Caution! Any installation  work  on the  ventilation  unit may  only  be carried  out  with the mains 
voltage disconnected! The ventilation unit is insulated in accordance with protection class II, a 
protective conductor connection is not required. 

Make sure  all connection  lines  are de-energized  before connecting  the  ventilation unit to the 
power  supply!  (Disconnection  from  power  supply  with  at  least  3  mm  contact  opening,  e.g. 
fuse) 

Each circuit connected to the ventilation system must be fitted with residual current protection 
(e.g. RCD switch)!  

Electrical connections must be carried out by qualified staff only! 

4.1  

Automatic operation with humidity control according to DIP switch position of the  

 

control board. 

 

Comfort control: Humidity controlled operation 

 

Basic control: Interval switching possible 

 

4.2  

With remote control (0 - 10 V) 

 

The remote control input is divided into two ranges. In the range of 0-5 V the level is  

 

 set absolutely, i.e. with highest priority (corresponds to DIP 6,7 with switched L1 ). In the 

 

range of 6-10 V only the base load is set (corresponds to DIP 1,2). In the range of  

 

0-0.4 V the fan operates autonomously. 

 

  

 

 
 
 
 
 
 
 
 
 

4.3

Depending on the control board, DIP switch position and module: 

 

With run-on time (basic control): Deactivation of the run-on functions (L2), conti-  

   

nuous operation basic ventilation or OFF according to DIP switches 1 and 2 swit- 

               

chable to regulated ventilation (L1) according to DIP switches 6 and 7 

 

With humidity control (comfort control): Humidity control can be deactivated (L2),  
switchable to regulated ventilation (L1) 

 

 

Note: 

No light coupling possible  with VDE-compliant installation  

 

((R) Bridge) 

 

4.4  

Depending on control board, DIP switch position and module: 

 

Single-stage operation, switchable to regulated ventilation 

 

Continuous operation basic ventilation and run-on time-controlled regulated ventila- 
tion 

 

Humidity control, switchable to regulated ventilation 

 

Run-on time-controlled regulated ventilation 

 

Note: 

Use a two-pole switch to switch the room lighting simultaneously with the  

regulated ventilation! 

 

4.5  

Direct connection to TAC via F+ and F-. 

Step 0:  0,6 V - 0,9 V 
Step 1:  1,1 V - 1,4 V 
Step 2:  1,6 V - 1,9 V 
Step 3:  2,1 V - 2,4 V 
Step 4:  2,6 V - 2,9 V 
Step 5:  3,1 V - 3,4 V 
Step 6:  3,6 V - 3,9 V 
Step 7:  4,1 V - 4,4 V 
Step 8:  4,6 V - 4,9 V 

Step 1:  6,1 V - 6,4 V 
Step 2:  6,6 V - 6,9 V 
Step 3:  7,1 V - 7,4 V 
Step 4:  7,6 V - 7,9 V 
Step 5:  8,1 V - 8,4 V 
Step 6:  9,6 V - 8,9 V 
Step 7:  9,1 V - 9,4 V 
Step 8:  9,6 V - 9,9 V 

Area 
absolute 
level

 

Base load 
level area

 

4 Electrical Connection 

Summary of Contents for LUNOS

Page 1: ...o ec Please pass on to user E169 NO 02 21 v 08 2 1 2 3 4 NO Tips 2 EN Hints 2 5 NO Leveranseinnhold 3 EN Delivery units 3 NO Montasje 3 EN Assembly 3 NO Elektrisk tilkobling 5 EN Elektrical connection 5 NO Filtervedlikehold 5 EN Filter replacement 5 6 NO Tekstdel Beskrivelse 6 EN Text part description 13 2 25 m 1 1 0 2 1 2 0 ...

Page 2: ...3 040078 V EC 2 E D 3 3 B 3 2 3 A 3 1 4 G D F 3 4 3 5 3 7 3 8 3 6 Q 90 90 ...

Page 3: ...isk strøm Advarsel Ved alt montasjearbeide på ventilasjonsutstyret skal nettspenning være frakoblet OBS Elektrisk tilkobling til nettspenning 220 Volt AC skal gjøres av autorisert personell I henhoold til gjeldende forskrifter OBS Utstyret skal ikke betjenes eks filterbytte renhold av barn eller personer som grunnet fysisk sensorisk eller mentale evner uerfarenhet eller uvitenhet ikke er i stand t...

Page 4: ...skal kun gjøres ved allpolig frakoblet nettspenning Tillegg av installasjoner og elektriske komponenter i dette ventilasjonssystemet tillates ikke 3 1 Eventuelle beskyttesesdeksler fjernes fra kapslingen Kontrollér elektriske tilkoblinger og posisjonen for tilkoblingskontakt A 3 2 Ventilatorinsatsen klikkes på plass og nettilkoblingen skrus fast B 3 3 Styrekort E settes på plass I filterrammen D o...

Page 5: ...9 V Områder for absolutte trinn Områder for grunnavtrekk 4 3 Avhengig av styrekort innstilling av DIP bryter og modul Med forsinket utkobling Basisstyring Deaktiverer forsinket utkobling L2 kontinuerlig grunnavtrekk eller AV i henhold til DIP bryter 1 og 2 kan kobles ved behovsavtrekk L1 Med fuktighetsstyring Komfortstyring Deaktiverbar fuktstyring L2 kan kobles ved behovsavtrekk L1 Tips Styring a...

Page 6: ... spenning på L2 blir alle spesialfunksjon deaktivisert forsinket innkobling etterdriftstid intervalldrift og fuktighetsstyring I de første to timene etter at ventilatoren har blitt tilkoblet nettspenning vil ventilatoren gå med en kapasitet tilsvarende den målte relative luftfuktighet Fuktighetsstyring Intervall AV Intervall PÅ Ventilator går I 30 minutter med behovsavtrekk hver 4 time Intervall P...

Page 7: ... Electrical Connection 16 Setting the DIP Switches 17 Humidity Control 18 Filter Change Cleaning Additional Parts and Replacement Parts 19 Installation Instructions EN About These Instructions Safety Instructions Range of Application Disposal 6 14 1 Notes Technical Data Power supply 200 240 V AC 50 60 Hz Remote control input 0 10 V DC Protection class II Protection type IPX5 Air volume flow OFF 15...

Page 8: ...ms for further fan functions available on request Caution Any installation work on the ventilation unit may only be carried out with the mains voltage disconnected The ventilation unit is insulated in accordance with protection class II a protective conductor connection is not required Make sure all connection lines are de energized before connecting the ventilation unit to the power supply Discon...

Page 9: ...ge DIP switches 1 2 and the regulated ventilation stage DIP switches 6 7 This ensures that the exhaust air volume flow is constantly adjusted to the room air humidity and room temperature thus achieving an optimum level of comfort There is only as much ventilation as necessary but also only as little as possible which saves energy prevents over humidification of the apartment and avoids structural...

Page 10: ...r physical sensory or mental capacity or due to their inexperience or lack of skills Pack of 3 filters 2 FSI R Order no 039 721 Control board basic variant 5 EC ZI Order no 040 080 Control board comfort variant 5 EC FK Order no 040 081 Control board basic variant up to 90 m h 5 EC ZI90 Order no 040 126 Control board comfort variant up to 90 m h 5 EC FK90 Order no 040 127 Control board for basement...

Page 11: ...21 ...

Reviews: