Product Description
The wall-mounted Occupancy Sensor saves energy and adds
convenience by accurately detecting when an area is occupied
or vacant
This device is wireless, powered by indoor light, and uses a
passive infrared (PIR) sensor to detect motion. The occupancy
sensor transmits RF signals to control lighting using the WLVD.
Features Include:
-
Sends wireless messages to other devices when motion is
detected
-
Harvests ambient solar energy to power the sensor and
wireless communication
-
Mounts flush to a wall or in a corner
-
Works with other sensors for enhanced occupancy
tracking
-
Interchangeable lenses for tailored sensor coverage
-
Built-in test to confirm operation at installed location
-
Supplemental battery or alternative power supply options
for extreme low-light conditions
Specifications:
Power Supply Indoor light energy harvesting
Optional: Supplemental battery or 2
wire connector for external power
RF Communications EnOcean 902 Mhz (EOSCU)
RF Transmission Range 80 ft. (25 m)
Motion Sensing Range Up to 100 ft. (25m)
(refer to coverage diagram)
Minimum Operating Light 50 lux (for auto-off only)
Startup Charge Times (operation from empty energy storage)
Linking Only 4 minutes @ 100 lux
1.5 minutes @ 200 lux
Motion Transmission 6 minutes @ 100 lux
3.5 minutes @ 200 lux
Light/Walk Test Modes 5.5 hours @ 200 lux
Time to Full Charge 9 hours @ 200 lux
Sustaining Charge Time 3 hours per 24 hours @ 200 lux
Motion Transmission Interval 2 minutes
Unoccupied Transmission 10 and 30 minutes since last motion
Heartbeat Transmission
Interval (optional)
Disabled by default
Enabled: 1 heartbeat @ 1 hr interval
(after unoccupied message)
Operating Life
(in Total Darkness)
48 hours (after full charge)
Supplemental Battery Life
(Continuous battery free operation standard)
Infrequent Bright Light
20 Years (200 lux for 2 hrs/day, 5 days/week)
Consistent Low Light
15 years (50 lux for 5 hrs/day, 7 days/week)
Total Darkness
6.5 years
EnOcean Equipment Profile
(EEP)
A5-07-01
Dimensions 5.83" L x 2.52" W x 1.80" D
(148mm x 64mm x 46mm)
Weight 4.1 oz (116 g)
Mounting Height 6-8 feet recommended
Environment Indoor Use Only
14° to 104°F (-10° to 40°C)
20% to 95% relative humidity
(non-condensing)
Agency Compliance EOSWU &EOSWC - FCC, IC, RoHS
EOSWA - RoHS
* Sunlight, bright lighting or battery can be temporarily used to significantly
shorten startup charge times. Specified lux values are for typical fluorescent
lighting. Lux level requirements for LED and other types may vary. For lux
reference, OSHA standards require a minimum of 323 lux for office areas.
© Lauren Illumination, 2015
Page 1
Package Contents
Tools Required
-
Occupancy Sensor
- Power Drill, 3/16” Bit
-
2 Screws, 2 wall anchors - Screwdriver
-
1 wide angle lense
- Light meter
(installed)
- Battery (CR2032) for testing
-
1 long range lens
Installation Guide
Model: WOSW
Occupancy Sensor – Wall Mounted