- 32 -
COMMUNICATION INTERFACE
WRITING
READING
Write the value in W1.
Send command 1003 to CMDR.
Send command 1002 to CMDR.
Read the value in R1.
MAXIMUM WEIGHT
(from 0 to full scale; default: 0): settable and displayable maximum weight. If the displayed
weight exceeds the maximum weight by 9 divisions, the
message is displayed; if in the
formulas programming the weight value set is greater than this value, the
message is
displayed and the value will not be stored. By setting 0, the function is disabled.
COMMUNICATION INTERFACE
WRITING
READING
Write the value in W1.
Send command 1001 to CMDR.
Send command 1000 to CMDR.
Read the value in R1.
SAFE EMPTYING TIME
(from 0.0 to 999.9 seconds; default 5.0): time that is necessary for a perfect emptying of the
scale. The instrument waits for this time during the unloading phase (CYCLE END closed), after
reaching the minimum weight and before opening the CYCLE END contact to obtain a perfect
emptying of the scale.
COMMUNICATION INTERFACE
WRITING
READING
Write the value in W1.
Send command 1005 to CMDR.
Send command 1004 to CMDR.
Read the value in R1.
WAITING TIME
(from 0.0 to 999.9 seconds; default 5.0): time elapsing between the SET end batching and
the CYCLE END closing to allow the weight to get steady. This waiting time is only required if the
automatic fall is programmed and/or consumption is enabled and/or a tolerance value has been
programmed and/or the wait for remote confirmation is enabled.