Before installing, draw an installation plan showing the placement of the 

fixings guides, heating cables, floor sensor, and junction box or boxes.
It is important to mark the location of the cold lead joint on the plans. The 

cold lead is the non-heating portion of the cable that will run in the wall to 

connect the system to the thermostat. The heating cable shall not extend 

beyond the room or area in which it originates.
Marking the heating cable layout on floor plan makes it easier to trace back 

the heating cable for trouble shooting purpose. Keep such a layout filed 

after installation.
Before installing the heating cables, refer to the spacing guide below to 

ensure you have the correct number and size of heaters for the area you wish to heat. 

Installing the STRATA_HEAT

 Spacing Strips

When using 12" (305 mm) STRATA_HEAT™ Spacing Strips to secure the cable to the subfloor, use the following provisions to ensure 

proper spacing of the cable. The fixing guides included in the kit are 12" (305 mm) long with 1" (25 mm) spacing guides.  
The perimeter STRATA_HEAT Spacing Strips should be installed a minimum of 3 

inches (76 mm) away from the wall in the opposite direction to the cable runs 

(Additional stabilizing guides could be laid 40 inches / 102 cm apart across 

the floor). The STRATA_HEAT Spacing Strips can be secured to the floor using 

hot glue, nails, screws or strong double-sided tape
It may be necessary to cut the guides into smaller sections to accommodate 

irregular shaped rooms. The strips can be secured to the floor using hot glue, 

nails or screws. 
Once you have fitted the STRATA_HEAT Spacing Strips, the STRATA_HEAT Wire 

may be laid out.

Spacing Guide

For precise calculation of spacing between loops (OCS), we recommend you 

use the following calculation using the cable lengths given on page 4. For 

additional clarification please call our technical support line: Technical Service 

at 203-393-0010 Ext 235.

OCS (On Center Spacing) = Area (sq ft) × 12 or Area (m

2

) ×  129.2

 

 

                    Length

PLANNING YOUR INSTALLATION 

Summary of Contents for STRATA_HEAT 0802-0067-2

Page 1: ...al before attempting to install your STRATA_HEAT Wire Incorrect installation could damage the STRATA_HEAT Wire and will invalidate the warranty Globally Proven Construction Solutions Globally Proven C...

Page 2: ...l Insulation 8 Floor Coverings 8 Subfloor Preparation 9 Controlling Your System 10 Wiring Diagram 120V 11 Wiring Diagram 240V 12 Electrical Provisions 13 Testing the System 14 Planning Your Installati...

Page 3: ...inal outer jacket of PVC is given to make it sturdier and provide corrosion protection The heating cable is terminated at one end with a 10 3 1 m cold lead The conductor cores and ground braid are fac...

Page 4: ...2 365 111 3 73 110 147 61 91 122 0802 0398 2 398 121 3 80 120 160 66 99 133 0802 0083 4 83 25 3 17 25 33 14 21 28 0802 0100 4 100 30 5 20 30 40 17 25 33 0802 0133 4 133 40 5 27 40 53 22 33 44 0802 016...

Page 5: ...nstalling the floor covering for future reference DO ensure that the STRATA_HEAT Wire is separated from other heat sources such as luminaires and chimneys DO ensure that the minimum bending radius is...

Page 6: ...EAT Wire under permanent fixtures DON T commence installation on a mud job screed that has not been fully cured DON T use the STRATA_HEAT Wire system until you have allowed sufficient drying period fo...

Page 7: ...9 1 STRATA_HEAT WIRE SPECIFICATIONS 3 5 89 mm Spacing 240 Volt Area ft m Model Length ft m Wattage W Amps A Resistance 25 2 32 0802 0083 4 83 25 3 335 1 4 177 2 30 2 79 0802 0100 4 100 30 5 400 1 6 14...

Page 8: ...up to 5 hours to heat a room whereas a system with thermal insulation takes less than an hour If the LATICRETE STRATA_HEAT Wire is being installed onto a concrete base it is highly recommended that a...

Page 9: ...be applied and allowed to cure If the cable is being fitted to a solid floor it is essential that the concrete slab has been allowed to cure If using the HYDRO BAN Boards use a suitable cement based...

Page 10: ...Wire has a maximum resistive load of 15 Amps Please refer to the table on page 7 to calculate the amperage load for your particular system For smaller areas you may be able to utilize an existing cir...

Page 11: ...11 WIRING DIAGRAM 120V...

Page 12: ...12 WIRING DIAGRAM 240V...

Page 13: ...electrical metallic tubing or by other approved means The installation of electrical systems presents risks of fire and electrical shock which can result in personal injury Caution should always be ta...

Page 14: ...circuit Place one probe on the black wire Place the other probe on the yellow red wire for 240V Resistance can vary significantly depending on the ambient temperature and an allowance of 5 from the no...

Page 15: ...rovisions to ensure proper spacing of the cable The fixing guides included in the kit are 12 305 mm long with 1 25 mm spacing guides The perimeter STRATA_HEAT Spacing Strips should be installed a mini...

Page 16: ...as this may damage both the factory joint and or the heating element within Secure the joint to the subfloor using duct tape Do NOT completely cover the joint in tape as this may create air pockets r...

Page 17: ...floor probe into the channels and secure with fixing tape NOTE Do NOT run the cold lead wires and the floor sensor in the same conduit Installing the STRATA_HEAT Thermostat Instructions for the fitti...

Page 18: ...layers is 3 8 9 5 mm of thinset or adhesive When deciding between the single layer or the double layer method you should consider the following We do NOT recommend the single layer method if you will...

Page 19: ...s Now Install the STRATA_HEAT Wire into the gap which was created by the sleepers Carefully return the cold tail lead to the junction box or the STRATA_HEAT Thermostat alongside the STRATA_HEAT Wire a...

Page 20: ...r Energy consumption will vary depending on user preferences For lower energy consumption set the STRATA_HEAT Thermostat to optimum temperature setting Energy consumption can be minimized by turning t...

Page 21: ...er or LATICRETE You will need to locate the model information for the heater either on the product labels you kept or based on an invoice While incorrect grounding is the main cause for breaker trippi...

Page 22: ...22 NOTES...

Page 23: ...end user STRATA_HEAT Wire model number Resistance ohms Insulation Resistance M ohms Before During After Before During After Installation Address Date of Installation Electricians Details Name Signatu...

Page 24: ...24 FLOOR PLAN...

Page 25: ...your project with confidence n Customizable warranties are available to suit your specific project requirements CERTIFICATIONS LATICRETE materials are certified by independent laboratories throughout...

Page 26: ...26 NOTES...

Page 27: ......

Page 28: ...ICRETE Park North Bethany CT 06524 3423 USA l 1 800 243 4788 l 1 203 393 0010 l www laticrete com 2017 LATICRETE International Inc All trademarks shown are the intellectual properties of their respect...

Reviews: