background image

HALP-24-2L-LED-2XH

Larson Electronics, LLC

 

  Phone: (800) 369-6671 

 Fax: (903) 498-3364 

  www.larsonelectronics.com 

of 

2

 

INSTALLATION 

1.

Install fixture to surface with four mounting brackets (mounting hardware not included).

2.

Remove lens by releasing latches that secure the lens. The lens will suspend by the tethers inside the
fixture.

3.

Remove lamps.

4.

Twist wing nuts ¼ turn counter clockwise to release the ballast tray from the housing.

5.

Electrical voltages and frequency are listed on the ballast tray for reference.

6.

For supply connections use conductors suitable for min. 90° C.

7.

Connect internal wires per wiring diagram on ballast, and according to NEC requirements.

8.

Replace the ballast tray and twist wing nuts ¼ turn clockwise to secure.

9.

Install lamps.

10.

Replace lens and secure all latches.

MAINTENANCE 

Electrical and mechanical inspection of all components must be performed on a regularly scheduled basic, determined by 
the environment and frequency of use. It is recommended that inspection be performed a minimum of once a year. 

WARNING: 

ELECTRICAL POWER SUPPLY MUST BE “OFF” BEFORE AND DURING INSTALLATION AND

 

MAINTENANCE. INSTALLATION AND MAINTENANCE PROCEDURE MUST BE PERFORMED BY A TRAINED AND 
COMPETENT ELECTRICIAN.

 

1.

Inspect all contact wire terminals for tightness. Discoloration due to excessive heat is an indicator of a possible
problem and should be thoroughly investigated and repaired as necessary.

2.

Inspect contacts for signs of wear and replace if necessary.

3.

Clean exterior surfaces making sure nameplates remain legible.

If any part of the light  appears to be missing, broken, or show signs of damage—discontinue use immediately! This 
condition could  cause serious or fatal personal injury due to electrocution and/or equipment damage. Repair with the 
proper replacement part(s) before continuing service. 

SURFACE MOUNTING

Flange  type  aluminum  mounts  attached  at  each  end  of  the  fixture  enables  it  to  be  simply  secured  to  any  surface.  The 

mounts provide some shock absorbency protection while enabling the user to simply mount the fixture with the through-hole 

taps that protrude on each side of the fixture. The mounting holes are 14.91" inches on center apart along the top of this 

hazardous location light. The mounting holes are 9.5" inches on center across the top of the light.

PENDANT MOUNTING

This light fixture can hang from the ceiling suspected by rigid pipe. Each fixture is equipped with either two 1/2" or 3/4" NPT 

hubs on either side of the fixture. Operators will bring rigid pipe down to the threaded mounting ups. The wiring is fed down 

through the rigid pipe to one of the NPT hubs and tied to the fixture`s lead wires to complete the electrical connection. The 

remaining pendant hub provides support for the opposite end of the fixture.

USE AND CARE

Unauthorized modification may impair the function and/or safety of this device and could affect the life of the equipment. 

Always check for damaged or worn out parts before using the device. Store it in a secure place out of the reach of 

children when not in use. Inspect for good working condition prior to storage and before re-use.

 

 

REPLACEMENT PARTS

The 

HALP-24-2L-LED-2XH

 is designed to provide years of reliable performance. Should the need for replacement parts 

arise, please contact Larson Electronics. 

THESE INSTRUCTIONS MAY  NOT COVER ALL DETAILS OR VARIATIONS OF THIS PRODUCT FOR YOUR EQUIPMENT OR INSTALLATION REQUIREMENTS. 