background image

HAL-36-25W-LED-JB-1227-M

Larson Electronics, LLC

 

  Phone: (800) 369-6671 

 Fax: (903) 498-3364 

  www.larsonelectronics.com 

3

 of

 

4

 

Warning: 

Check product label for correct input voltage!

 

Attach supply line wires to the appropriate light fixture wires as shown 

in the diagram 

 

Secure each pair of wires according to the diagram. Utilize a junction box or 

similar  device  and  take  precautionary  steps  for  weatherproofing  all 

connections if installed in a location where water may come in contact with the 

unit. Ensure the unit is properly grounded and that wiring is done according to 

all local and national electrical/building codes. 

Exp Cord Cap 

Position  device  near  work  area  for  operation.  Run  cable  to  nearby  power 

source. Insert and twist-lock explosion-proof plug into a compatible receptacle within 

the hazardous environment. See 

plug operation

 below. 

PLUG OPERATION 

Electrical connection between plug and compatible receptacle is accomplished 

after plug fully inserts into receptacle and rotated clockwise. 

1.

Lift receptacle door and locate polarization on mating plug pin and

 

receptacle face. Insert plug straight all the way into receptacle until it

 

cannot go further.

2.

Rotate plug clockwise limit (37º), this closes internal contacts and

 

completes circuit. This also mechanically locks plug into receptacle so it

 

cannot be pulled out.

3.

To remove plug, push plug inward and turn to counterclockwise, pull plug

 

straight out.

MOUNTING

The HAL-36-25W-LED-JB-1227-M is equipped with two 200 lb magnets spaced evenly along the length of the light. The 

magnets allow for quick and secure mounting on flat, magnetic surfaces. The entire assembly weighs 2.5 lbs and measures 

35.88 inches in length, and 2.68 inches wide and 1.69 inches deep, making it ideal for mounting in areas where space is 

limited and a low profile fixture more readily installed.

VERSATILITY

The HAL-36-25W-LED-JB-1227-M is ETL approved for Class I Division 2 groups A, B, C and D locations. This unit carries 

an IP54 water resistant rating ensuring protection against limited ingress from dusts, dirt, and basic protection against light 

water spray landing directly on the fixture. This light is ideal for indoor or outdoor applications and industrial operations with 

hazardous location classification where dusty or wet conditions are commonly encountered.

MAINTENANCE 

Caution: 

To avoid personal injury, disconnect power to the light and allow the unit to cool down before performing 

maintenance. 

Warning: 

No user serviceable parts inside of fixture. Risk of electric shock. Removal of the lens will void the warranty. 

1.

Perform visual, mechanical and electrical inspections on a regular basis. We recommend routine

 

checks to be 

made on a yearly basis. Frequency of use and environment should determine this.  It is

 

recommended to follow 

an Electrical Preventive Maintenance Program as described in NFPA 70B:

 

Recommended practice for 

Electrical Equipment.

2.

The lens should be cleaned periodically as needed to ensure continued photometric performance.

 

Clean the 

lens with a damp, non-abrasive, lint-free cloth. If not sufficient, use mild soap or a liquid

 

cleaner.

3.

Inspect the cooling fins on the luminaire to ensure that they are free of any obstructions or

 

contamination (i.e. 

excessive dust build-up). Clean with a non-abrasive cloth if needed.

4.

Do not operate if the lens is cracked or damaged. All fasteners should be properly seated.

Reviews: