INSTALLATION CHECKLIST 

  Verify sufficient lubricant is on conduit plugs 

(recommend approximately 1/8” bead 
around the first thread of plug) and that all 
unused conduit entries on the cover module 
are closed with lubricated plugs. 

 

  Verify conduit plugs are installed to at least 

five (5) full threads into the cover module 
conduit entries. 

 

  Verify installed conduit plugs are torqued to 

42-52 ft.-lbs. for 3/4” plugs and 58-68 ft.-lbs. 
for 1” plug. 

 

  Verify supply wires are connected to 

luminaire wire leads (or terminal block) per 
wiring diagrams. 

 

  Verify all electrical connections are 

tightened. 

 

 
 

  Verify all wires are safely and neatly inside 

driver housing and not on top of wire 
terminal. Close driver housing onto cover 
module. 

 

  Verify captive closing screw is tightened to 

30 in.-lbs. (3.4N-m) and two (2) bosses on 
driver housing are in contact with cover 
module. 

 