MAINTENANCE

 

Before removing the cover from any such device for inspection or maintenance, the power supply circuit 
must be OFF. 

WARNING: 

To prevent risk of explosion, hammers and prying tools must not be used to remove covers 

off enclosures. Damage to the explosion proof flat machined surfaces on cover and enclosure may 
result. Handle covers carefully. Do not place them on surfaces that might damage or scratch the flat 
machined surfaces. 

Before replacing the cover, after it has once been removed, the flat ground joint surfaces must be 
cleaned as described in step 3 under installation. 

WARNING: 

To prevent risk of explosion, replace devices if the flat machined surface is damaged, 

scratched, dented, or corroded. Field rework of flat machined surfaces is not possible. 

CAUTION: 

Use 12 AWG copper conductors only. Insert the 

bare wire conductor(s) under the terminal clamp and securely 
tighten the screw(s). Note: Do not exceed 35 in-lbs. of torque. 

THESE INSTRUCTIONS MAY  NOT COVER ALL DETAILS OR VARIATIONS OF THIS PRODUCT FOR YOUR EQUIPMENT OR INSTALLATION REQUIREMENTS. 

SHOULD FURTHER INFORMATION NOT COVERED BY THESE INSTRUCTIONS BE REQUIRED, PLEASE CONTACT LARSON ELECTRONICS BY EMAIL AT 

[email protected]

 OR BY PHONE AT 

1-877-348-9680

 FOR FURTHER ASSISTANCE. 

PLEASE VISIT LARSONELECTRONICS.COM FOR 

WARRANTY

 AND 

RETURN

 INFORMATION.