Following steps required for installation -
1. Install un
it’s mounting accessory
per instructions supplied with the
mount.
2. Install
un
it’s pushbutton
test
station (purchased separately) per
instructions
supplied
with
the
station. Station must be wired to
fixture mount to provide a method
of disconnecting the supply source
from the unit. An example of how
this can be completed is shown in
Fig.1 for typical installation.
3. Verify that the supply voltage
available is 120V thru 277V.
4. The fixture comes wired for 120V
thru 277V operation from the
factory. Lamp
provided
with
fixture is to be installed in a non-
hazardous environment as follows:
(A) Unscrew and remove the
globe support assembly (B) from
the unit tank (C). Install lamp. Re-
attach globe assembly (B) to unit
tank (C). Attach fixture to the
installed
mount.
If
277V
application is desired refer to step
5.
CAUTION:
During installation or maintenance, care must be taken to avoid
scratching, nicking or chipping the glass globe.
5. Make sure the external threads at the top of the unit tank are free of any dirt,
metal chips or other foreign materials. Apply a thin coat of lubricant to the
threads.
NOTE:
Take extreme care not to cross thread the unit when installing into the
mounting accessory. Install the unit by threading into the mounting accessory; the
electrical contacts will automatically
engage. Be sure the unit is threaded tight. Tighten the set screw on the side of the
mounting accessory.
6. Energize unit and verify that proper charging of the fixture is occurring by
observing if the red charging indicator lamp inside of globe area is on.
7. Test emergency lamp operation by pressing PUSH-TO-TEST pushbutton of