background image

 

12 

The start up is now complete. To test the systems fire suppression interlock, and Auto Fan Control for IMC 507.1.1 
compliance, follow the Test Procedures in the next section. For operation information and system adjustments see 
System Operation section. 
 

                                                     

Test Procedures 

 

Testing of the System for IMC 507.1.1  Compliance:  Please read  complete  test  procedures  prior to 
attempting function test for Fire Marshal.  
 
Note: For timely automatic de-activation, the test should  be done in the following  order:  1) Auto-
Activation, 2) Fire System Activation, 3) Auto Shut-Shut Down. When the test is done in this sequence, 
the Micro-Switch trip will bypass the 30-minute  run timer initiated on start-up and the system will Auto-
Shut Down in 3-5 minutes. If not, the system will run for approximately 33 minutes before shutting down. 

 

1. 

Cycle power to the Control Box to reset the system prior to test. 

 

2. 

Place the light and fan switches in the “OFF” position. Indicator lights should be “OFF”. Fan(s) and light(s) should 
be de-energized prior to initiating the test procedures below. 

 

3. 

Conduct  the test by applying heat to any one  of  the hood sensor(s)  located  in the center of the hood(s),  in 
between  and in line with the light(s) and in front of the grease filters. 

Note:

 It does not require much heat. The 

palm of your hand or hot water should be enough. 

DO NOT USE A TORCH!  

When the hood sensor(s) detect a 

rise  in temperature  the fan(s) and light(s) will  automatically  energize.  Both  Fan and light indicator lights will 
illuminate indicating that power is going to the fan(s) and light(s).  For multiple hood systems, when any  hood 
sensor  detects a temperature rise, the fan(s)  and  light(s)  will automatically  energize  for all hoods connected to 
that  Control  Box. 

Note:

 

Allow the system to continue operating after the  automatic  activation  to perform 

fire system test described next. 

 

4. 

For this portion of the test, the system should still be operating in automatic mode, described above. The system 
is designed to shut down the  lights and  MUA  fan(s),  continue to run  the  Exhaust  fan(s),  and  provide 120V for 
shunt trip breaker(s) in Fire Mode. To conduct this test, simply trip the fire suppression Micro-Switch to simulate 
Fire Mode. The Exhaust fan(s) should continue to run, the light(s) and MUA fan(s) should shut off, the Auxiliary 
Contacts should change state and 120V should be provided for shunt breaker(s). After testing, place the Micro-
Switch back to the normal position. The light(s) and MUA fan(s) should re-energize. Shunt trip breakers will need 
to be reset, if applicable. The system will shut down automatically after the sensor(s) have cooled to the factory 
pre-set Low End Turn Off temperature of 88° F. (may be accomplished with cool water), and the system detects 
no additional rise in temperature, within 3-5 minutes. This will complete the test procedure.  

 

If the light and/or fan switch have been turned to the “ON” position the system is running in manual mode and will 
not shut off automatically, it must be manually shut down. The switches must be in the “OFF” position for the auto 
de-activation  portion of the system to function. In normal operation  there  will be  a  factory  set  30-minute  Initial 
Safety Timer that must elapse before the system will de-energize. For multiple hood systems, the warmest sensor 
must cool to the factory set point before automatic de-activation will occur. 

                                                  

 

System Operation 

 

To comply with the International Mechanical Code 507.1.1 the commercial kitchen exhaust system shall operate 
during the cooking operation and have automatic controls that will activate the fan(s) no more than 15 minutes 
after the first appliance under the hood has been turned on. 
 
The AFC (Auto Fan Control) will accomplish this by automatically activating the fan(s) and light(s) anytime a hood 
sensor detects a rise in temperature. The fan and light indicator lights will be illuminated indicating power is going 
to the fan(s) and light(s). The fan(s) and light(s) will continue to operate in Auto Run Mode until all of the following 
shut down conditions are met: the fan and light switches are in the “OFF” position, the factory set 30 minute Initial 
Safety Timer has elapsed, the cooking equipment has been turned off, the sensor(s) do not detect a temperature 
above the factory pre-set Low End Turn Off (88° F.) for 3-5 minutes.  
 

Summary of Contents for Auto Fan Control

Page 1: ...tch Enclosure may be recess mounted with optional trim ring Switches with LED indicator lights mounted on enclosure door for system operation Exhaust and Make Up Air MUA fan s are interlocked If hood fire suppression system is activated the lights and MUA fan s shut down The Exhaust fan s will continue to operate Temperature sensor s factory mounted in hood s Exhaust and MUA fan starter s 3 Ph or ...

Page 2: ...d AFC the Control Box will be housed in a 12 x 22 x 6 stainless steel enclosure and should be secured to a fixed wall near the exhaust hood s it controls Fig 1 Enclosure may be recess mounted with optional trim ring see Figure 2 Fig 1 Fig 2 ...

Page 3: ...o Control Box for fan s See wiring diagram F 1 or 3 Phase wired from Control Box to fan s See wiring diagram G 1 or 3 Phase power if Tempered MUA is provided wired from breaker panel to Tempered MUA unit Note If Tempered MUA is provided the input power wiring for the Tempered MUA unit must be connected directly from the breaker panel G and a separate Run Stop control circuit connected from the Con...

Page 4: ...ng sensor between a light and end of the hood may be necessary on shorter hoods CAUTION If sensor is located too close to a light fixture the heat generated could activate the system The sensor s should be centered between lights Wiring Instructions The Larkin AFC components are all prewired The field wiring required to connect the Control Box to the hood s and breaker panel should be made in acco...

Page 5: ... operate See Heated MUA unit wiring diagram Note The input power wiring for Tempered MUA unit must be pulled from the breaker panel directly to the Tempered MUA unit Only control wiring should be connected from the AFC control box to the Tempered MUA unit Field Wiring Requirements for Control Panel Control Circuit Field wire 120 VAC 1 Phase 15 AMP to the Control Panel terminals Control Hot CH Cont...

Page 6: ...nsor terminals S1 located in the Control Box 22 AWG Min For a system controlling more than one hood connect the second hood sensor to terminals S2 the third sensor to terminals S3 and the fourth sensor to terminals S4 Sensors must be wired separately The corresponding Sensor Dip Switch must be in the ON position for every sensor connected to the terminal strip If a dip switch is in the on position...

Page 7: ...lead from the Micro switch to the Fire Switch Common FSC terminal in the Control Box Connect the Normally Closed NC lead from the Micro switch to the Fire Switch Normally Closed FSNC terminal in the Control Box Isolate the Normally Open NO lead from the Micro switch WARNING DO NOT APPLY VOLTAGE THROUGH MICRO SWITCH THIS WILL CAUSE DAMAGE TO THE CONTROL BOARD See micro switch mounting options on pa...

Page 8: ...l to the correct terminals in the Control Box for each fan being controlled Fan Output Power From Contactor s or Starter s Field wire output power to proper fan from contactor s or starter s terminals T1 and T2 1 Phase or T1 T2 and T3 3 Phase Check rotation of fan s Note Exhaust fan s will move some air in reverse See rotation arrow on fan Changing rotation may be accomplished by reversing any two...

Page 9: ...wiring in same conduit as input power circuits high voltage NOTICE Remove jumper from terminals R and G in the Tempered MUA unit Note The input power wiring for the Tempered MUA unit must be pulled directly from the breaker panel to the Tempered MUA unit Shunt Trip Breaker Connection Field install wiring from the Control Box terminal Shunt Trip Hot STH to the trip connections on the shunt trip bre...

Page 10: ...ed next to the exhaust hood s it controls See Pg 2 Are two separate circuits 120VAC 15AMP control and 120VAC 15AMP hood lights connected from breaker panel to Control Box per NEC See Pg 5 Are hood lights connected from the Control Box to the hood light junction box per NEC See Pg 5 Are hood sensor s connected from hood s to Control Box One sensor per hood or hood section Check dip switch position ...

Page 11: ...ing equipment should be off and fan s should not be operating If the fan s and light s come on with the switches in the OFF position the temperature sensor in the hood has detected a temperature rise If only the Exhaust fan s come on immediately check for proper connection of Fire System Micro Switch See Pg 7 or check that the Fire Suppression system is not in the discharged position With the fan ...

Page 12: ... s and provide 120V for shunt trip breaker s in Fire Mode To conduct this test simply trip the fire suppression Micro Switch to simulate Fire Mode The Exhaust fan s should continue to run the light s and MUA fan s should shut off the Auxiliary Contacts should change state and 120V should be provided for shunt breaker s After testing place the Micro Switch back to the normal position The light s an...

Page 13: ...pt adjusting controller before contacting customer support at 800 322 4036 The AFC system is designed to shut down the light s and supply fan s and continue to run the exhaust fan s in the event of fire and activate two Normally Open Normally Closed NO NC spare dry contacts may be used for building alarm horn strobe etc Terminal STH Shunt Trip Hot will also provide 115 VAC for shunt trip breaker i...

Page 14: ...14 See Pg 7 ...

Reviews: