Lanry Instruments
www.lanry-flow.com
- 21 -
Display & Output Model
c) RS485 Settings
Baud rates
– Support Baud rates from 4800 to 19200
Data Bits
– 8 data bits (7 data bits is not valid setting for Modbus RTU)
Parity Bits
– Even, Odd and None
Stop Bits
– 1
Default settings will be 9600,8,N,1
.
d) Modbus Registers
The below list of parameters will all be located in the holding registers.
Register
address
Size
(Reg)
Mode/Access Data Type
Description
00
4
Read only
float
Velocity
02
4
Read only
float
Flow rate
04
8
Read only
double64
Net accumulation
08
8
Read only
double64
Positive cumulation
12
8
Read only
double64
Negative cumulation
16
4
Read only
hh/mm/ss
Time in BCD format
18
4
Read only
yy/mm/dd
Date in BCD format
20
4
Read only
uint
Device state
22
4
Read only
uint
ESN
24
8
Read only
double64
Net accumulation for special date
28
8
Read only
double64
Pos accumulation for special date
32
8
Read only
double64
Neg accumulation for special date
36
4
Read/Write
yy/mm/dd
Set special date in BCD format
38
4
Read/Write
uint
Display control
40
4
Read/Write
uint
Rs485 control
42
4
Read/Write
uint
User control
48
4
Read/Write
uint
RS485 Retention time
50
4
Read/Write
float
Battery level
52
4
Read/Write
float
Software version
62
4
Read only
float
Pipe lose parameter