Maintenance
83/88
Changing the Communication Unit in f9 Meters
1. De-install the meter (
see page 52
).
2. Switch off the voltage. The phase voltage display ( L1 L2 L3)
disappears.
3. Switch off tariff inputs and synchronisation input. Check if the
corresponding indicators disappear from the display.
4. Switch off the voltage for the additional power supply.
5. Withdraw the meter from the rack.
6. Remove the seals at the back of the housing and remove the housing.
7. Remove the communication unit (or dummy).
8. Carefully insert the new communication unit ensuring the plug and
socket are properly engaged.
9. Connect the connecting wires to the terminals of the communication
unit.
10. Carry out functional tests as described in the relevant communication
unit manual to ensure it is functioning correctly.
11. Replace the housing and re-seal.
12. Install the meter (
see page 47
).
Summary of Contents for ZFQ202
Page 4: ...Landis Gyr H 71 0200 0215 f en ZMQ202 ZFQ202 User Manual 4 88 ...
Page 28: ...Landis Gyr H 71 0200 0215 f en ZMQ202 ZFQ202 User Manual 28 88 Description of Unit ...
Page 54: ...Landis Gyr H 71 0200 0215 f en ZMQ202 ZFQ202 User Manual 54 88 Installation De installation ...
Page 66: ...Landis Gyr H 71 0200 0215 f en ZMQ202 ZFQ202 User Manual 66 88 Operation ...
Page 74: ...Landis Gyr H 71 0200 0215 f en ZMQ202 ZFQ202 User Manual 74 88 Service ...
Page 84: ...Landis Gyr H 71 0200 0215 f en ZMQ202 ZFQ202 User Manual 84 88 Maintenance ...
Page 86: ...Landis Gyr H 71 0200 0215 f en ZMQ202 ZFQ202 User Manual 86 88 Disposal ...