Landis+Gyr ULTRAHEAT T150 Operating And Installation Instructions Download Page 4

 

 

 

Gyr GmbH 

Subject to change without prior notice 

17.11.2021 

6. 

Functional Details 

The operating hours are counted from the first connection of the 
power supply.  
Missing  hours  are  summated  if  there  is  an  error  and  the  flow 
meter is thus unable to take a measurement. 
Operating  hours  and  missing  hours  can  be  reset  through  the 
service software. 

 

Note:

  Detailed 

information’s  on  resetting  operating 

hours and missing hours with the service software you 
will find in the UltraAssist user manual. 

Volume  readings,  maximum  flow  rates  and  missing  hours  are 
stored monthly for 36 months. 
The  device  number  and  the  firmware  version  number  are 
issued by the manufacturer. 

7. 

Technical Data 

 

Note:

  The  information  on  the  flow  meter  must  be 

observed! 

General 

 

Measuring accuracy 

Class 2 or 3 (EN 1434) 

Environment class 

A (EN 1434) for indoor installation 

Mechanical class 

M1 *) 

Electromagnetic class 

E1 *) 

*) according to 2014/32/EU Directive on Measuring Instruments 

Ambient humidity  

< 93 % rel. humidity at 25 °C, without condensation 

Max. height 

2000 m above sea level 

Storage temperature 

20 … 60 °C

 

Electronic unit 

 

Ambient temperature 

5 … 55

 °C 

Housing protection rating 

IP 54 according to EN 60529 

Power supply 

Battery for 5 or 9 years 

Optical interface 

Standard, EN 62056-21 

Communication 

Pulse output 

Separability 

Always, optional cable length  

Pulse output 

 

Type 

Open drain

 

Dielectric strength 

500 V

eff

 against ground, galvanic insulated 

Pulse significance 

Optional 

Pulse length 

Optional 

Pulse sequence 

In packages every 0.5 s (not equally spaced) 

Cable length  

2 m  

Voltage 

Maximal 30 V 

Current 

Maximal 30 mA 

Voltage drop 

< 0.3 V at 10 mA 

Polarity 

bipolar 

Volume measurement unit 

Protection class 

IP 54 / IP 65 according to EN 60529 

IP 68 (at qp 150) according to EN 60529 

Mounting place 

Hot side / cold side  

Installation position 

Any 

Flow straightening 

None 

Measuring range 

1:100 resp. 1:50 

Temperature range 

5 … 130 °C

 

National type approvals may be different. 

recommended

 

 

heat application 

10 … 130 °C

 

cooling application 

5 … 50 °C

 

Maximum overload 

2.8 x qp 

Nominal pressure 

PN16 (1.6 MPa; PS16), PN25 (PS25)  

 
 
 
 
 
 
 
 
 
 
 
 
 