D000059880 en a – S560 – Smart Meter Gateway – Technical Data
Tariffication application
- TAF1 Data economical tariff
- TAF6 Retrieval of values when needed
- TAF7 Meter values measurement
- Further TAFs upgradable in field
Non-functional requirements
Technical lifetime
20 years
Firmware update
Image-size <1.5 MB
Functional requirements
Physical operational status
<10 s
Specifications
Power Supply
Mains operation
230V
Operation voltage
1x230 V
Operation range
0.8 U
n
to 1.15 U
n
Frequency 50
Hz
Current drain (Capacitor loaded)
Without communication
4.5 W / 7 VA
Active communication over LTE
7 W / 9 VA
Power reserve RTC (Capacitor loaded)
72 h
Power jack
Phoenix MSBTVA 2,5/3-G-5.08
WAN Interface
LTE modem
WAN-1
LTE-Modem Type
integrated
GSM 850/900
Class 4 (2W, 33dBm)
GSM 1800/1900
Class 1 (1W, 30dBm)
EDGE 850/900
Class E2 (0.4W, 26dBm)
EDGE 1800/1900
Class E2 (0.5W, 27dBm)
UMTS 900/2100
Class 3 (0.25W, 24dBm)
LTE 800/1800/2600
CAT1
(0.2W, 23dBm)
Antenna jack
FAKRA-Connector
Bordeaux, violet, coding D
Impedance 50
Ohm
SIM card
SIM Card Format
ID-000-Format
(size ca. 25 × 15 mm)
Slot in sealed area with push-push locking
LMN Interface
LMN wired (RS485)
LMN-1
Maximum load
3.5W (20°C)
Baud rate
921.6 kBits/s
Jack
RJ12 / 6p6c
LMN wireless (wM-Bus)
FAKRA Connector
Signal Blue, Coding C
Frequency 868.95
MHz
HAN Interface
HAN interface (covered by flap)
HAN
Jack RJ45
CLS interface (in sealed area)
CLS
Jack RJ45
Status-Interface
LED indicator (front)
- PWR Powered, Operational State, Critical Error
- TLS
Active TLS Session of Type Management
- LMC
Local Meter Connect
- wMT
Wireless M-Bus Traffic
- RSSI
Received Signal Strength (Mobile)
Controllable Outputs (Option)
Controllable outputs
N/O contact
3 Solid State Relays
Change Over Contact
1 bistable Relay
Max. Voltage
230V AC
Max. Current
90 mA (20°C)
Environment
IEC-specific Data
Electromagnetic compatibility
Surge Immunity
4 kV, 50 Hz (IEC 610-0-4-5)
Electro Static Discharge
Air 8 kV /Contact 4 kV (IEC 610-0-4-2)
Electrical Fast Transient
4 kV (IEC 610-0-4-4)
Impulse Voltage
7 kV, 1.2/50
μ
s (IEC 62052 11)
Electro Magnetically Field Immunity
10 V/m (IEC 610-0-4-3)
Environmental
Temperature range
Ambient Temperature Operation –25°C to +55°C
Ambient Temperature Storage
–40°C to +70°C
Protection class
Protection Class
IP51 (IEC 60529)
With module cover
Isolation
Protection Class II
Over Voltage
Category III
Approvals and certifications
CC-PP-0073 protection profile
Planned
June
2017
PTB 50.8 type approval test
G1-Gateway
Planned April 2017
TR-03109 BSI conformity
TR Version 1.0
self-declaration
TR Version 1.1
depending on TR1.1 launch