Landis & Gyr ULTRAHEAT T550 Installation Instructions Manual Download Page 5

 

Gyr GmbH 

Subject to change without prior notice 

08.05.2017 

 
 

Select first module function for module 2  
(CE or C2) 

 
 
 

Select second module for module 2  
(CV or CT or RI) 

 

Select maxima measurement period  
(7.5, 15, 30, 60 min / 3, 6, 12, 24 h) 

 

Pulse value 

 

Mounting place of the flow (here: cold side) 

 

Return to normal mode 

* Ensure that sensible values are entered. The calculator does not carry out a plausi-
bility test. This means that incorrect values can also be entered (e. g. month > 12). 

 

Note:

  The  calculator  can  be  parameterised  even  if 

the modules have not yet been installed. 

4.3 

Parameterisation  of  pulse  value  and  mounting 
place of the flow sensor 

 

Attention: 

Calculators  with  one-time  adjustable 

pulse  value  and  adaptable  mounting  place  being 

characterized by:

 

 

The pulse value must be set in the para menu before the first 
use.  The  right  mounting  place  of  the  flow  sensor  must  be 
checked

. As long as the pulse value hasn’t yet been entered, 

the mounting place can be adapted. 

 

Pulse value 

 

Mounting place of the flow sensor (here: cold side)  

 

Return to normal mode (manual) 

Both entries will be adopted with the return in the normal oper-
ation and subsequently cannot be changed anymore!  
LCD display will adopt automatically.  

4.4 

Call up parameter operation 

Proceed as follows to call up the parameter operation: 

 

Hold the service button for 3 seconds until 

 appears on the LCD. 

 

Press button 1 to switch the display until 

 

appears on the LCD. 

 

Press button 2 to select the menu. 

 

Note:

 To reset error F8 or the maxima press button 2. 

4.5 

Selecting parameters 

To select a parameter proceed as follows: 

 

To switch the display press button 1. 

 

To activate the parameter to be changed press button 2. 

4.6 

Parameterisation 

For parameterisation proceed as follows: 

 

To change the blinking value press button 2. 

 

To enter the set value press button 1. 

The next digit to the right blinks. Repeat the steps above for all 
digits. 

 

The LCD displays a star symbol briefly to confirm. 

If inputs are incorrect, parameterisation can be repeated. 

4.7 

Completing parameterisation 

To leave the parameterisation operation proceeds as follows:  

 

Hold button 1 until the LCD shows 

 

Press button 2. 
 

4.8 

Cancelling Input 

To close the parameterisation proceeds as follows: 

 

Press the service button during parameterisation (ESC 
function). 

The LCD display shows the last valid value. 

4.9 

Service software 

With  the  service  software,  tariffs and communication modules 
can be set in parameterisation mode 

5. 

Getting started 

 

Attention: 

Calculators  with  one-time  adjustable 

pulse  value  and  adaptable  mounting  place  being 

characterized by: 

 

 

Attention: 

At  calculators  with  one-time  adjustable 

pulse value, the pulse value must be adjusted during 
commissioning  in  accordance  with  the  flow  sensor 
and the mounting place must be checked! 

At long as not the pulse value has be set,  the calcu-
lator not cumulated energy and volume. 

The mounting place can be adapted and fully locked 
by entering the pulse value. 

For activation proceed as follows: 

 

Put the housing cover in position and press it gently until all 
the lugs click into place audibly. 

 

Check the measured values for flow and temperatures for 
plausibility. 

 

Fit the user locks to the electronic unit and the temperature 
sensors.  

 

Note the values. 

Recommendation: 

Reset the maxima and the missing time. 

Error messages for incorrect installation: 

 

Error “negative temperature difference“ 

Check whether the temperature sensors are installed 
correctly. If the sensors are not installed correctly, change 
the installation position of the temperature sensors. 

 

 

Heat meter

Temperature sensor in the flow-pipe with higher tempera-
tures; temperature sensor in return-pipe with lower tempera-
ture 

 

Cooling meter: 

Temperature sensor in the flow-pipe with lower temperatures; 
temperature sensor in return-pipe with higher temperature 

 

 

Note:

 When the appliance is idle, these messages may 

appear even if there has been no incorrect installation. 

6. 

Display / priority rating 

The  display is limited to up to 7  digits. At pulse parameteriza-
tion, the resolution will adapt automatically.  

The display resolution can be selected from the following: 

Pulse 

Energy 

Energy 

Volume 

Flow 

Power 

[l/p] 

[MWh] 

[GJ] 

[m³] 

[m³/h] 

[kW] 

0000.001 

0000.001 

00000.01 

000.001 

00000.1 

2.5 

0000.001 

00000.01 

00000.01 

000.001 

00000.1 

10 

00000.01 

00000.01 

000000.1 

000.001 

00000.1 

25 

00000.01 

000000.1 

000000.1 

000.001 

00000.1 

100 

000000.1 

000000.1 

0000001 

0000.01 

000001 

250 

000000.1 

0000001 

0000001 

0000.01 

000001 

1.000 

000000.1 

0000001 

0000001 

0000.01 

000001 

2.500 

000000.1 

0000001 

0000001 

0000.01 

000001 

Summary of Contents for ULTRAHEAT T550

Page 1: ...d As far as disposal is concerned the calculator is a waste electronic appliance in the sense of European Directive 2012 19 EU WEEE and it must not be disposed of as domestic waste The relevant national legal regulations must be observed as the appliance must be disposed of via the channels provided for this purpose The local and currently valid legislation must be observed The calculator may cont...

Page 2: ...erature sensors into the pockets ball valves or T pieces The end of the temperature sensors must reach at least to the centre of the pipe cross section Seal the temperature sensors to protect against manipula tion Put the housing cover in position and press it gently until all the lugs click into place audibly 3 2 Connection of flow sensor Note The flow sensor must be installed at the same circuit...

Page 3: ...and press it gently until all the lugs click into place audibly Installing power supply module Note The 110 V 230 V connections may only be made by an electrician To install a power supply module proceed as follows Move the red locking hatch to the left Move the right outside rubber sleeve upwards and out wards Pull the sealing plug Thread the module s mains voltage connetion cable through the sle...

Page 4: ...n modules Note You will find the technical details and data on communication modules in their documentation Note You will find the permitted combinations in the T550 UC50 technical description Note The meter recognises the inserted modules automatically 30 seconds at most after installation and is ready for communications or pulse output Note The type of module inserted can be displayed within the...

Page 5: ...t To close the parameterisation proceeds as follows Press the service button during parameterisation ESC function The LCD display shows the last valid value 4 9 Service software With the service software tariffs and communication modules can be set in parameterisation mode 5 Getting started Attention Calculators with one time adjustable pulse value and adaptable mounting place being characterized ...

Page 6: ...ary in exchange with F1 Interruption in the hot side tempera ture sensor Check hot side temperature sensors replace if necessary F2 Interruption in the cold side tem perature sensor Check cold side temperature sensors replace if necessary F3 Electronics for temperature evalua tion defective Exchange the calculator F4 Problem with the power supply Battery flat Check connection Change battery F5 Sho...