
89
10 Correcting Faults
10.1.2
F300K Error Codes
NOTICE
H and U processor
The F300K reports errors of the H and U processors. The same error code contents are dis-
played with the same number. They are differentiated by means of a preceding H or U. The
operating hours when the error occurred and additional information are displayed in the error
menu.
No.
Description
017
Mode selection
External error or internal hardware error
–
no or more than one BA activated
018
Periodic signal
Signal frequency [Hz]
–
Sensor detects lamplight
–
strong resonance in burner chamber
027
Excess temperature
Warning temperature’s limit value exceeded
–
Ambient temperature is too high
035...
039
Communication with internal UI
–
Activate terminating resistor in UI or when accumulating change F300K or UI
035
Input buffer overflow internal bus
036
Communication with internal UI
037
Acknowledge error internal bus
038
BusOff Bus-A
039
Error-warning-level reaches internal bus
070
Power supply
Voltage breakdown or voltage interuption
–
24V DC disturbed from outside
071
Password generation
No PW of level 4 produced
–
Repeat input
075...
079
Communication via external BUS
–
Disorder in the wiring
–
Termination resistor incorrect
–
when accumulating change F300K or UI on the bus
075
Input buffer overflow
076
Output buffer overflow
077
Acknowledge error
078
BusOff
079
Error-warning-level reached
093
EEPROM writing error
Summary of Contents for F300K IR-2
Page 2: ......
Page 26: ...25 5 User Interface 5 2 Menu tree ...
Page 31: ...30 6 Commissioning Marking information on the device Example F300K F300K UI FB30 Warning e g ...
Page 121: ...120 14 Appendix 14 3 EU Declaration of Conformity ...
Page 122: ...121 14 Appendix ...
Page 125: ...124 14 Appendix ...