Operation
Examples:
Example of inactive control, if the O
2
controller is not permitted to take over.
Example of active dynamic test
D2 ... dynamic test active, CO
e
120 ppm
6.1.5
Display and Interpretation of the Operating Modes
I - O
2
actual value
II - CO
e
value
a
Edge position:
"-"
Air would be reduced
"+"
Air would be increased
b
11
11 optimisation steps have
taken place
c
big "C" means
optimisation dur-
ing increasing firing rate
small "c" means
optimisation
during decreasing firing rate
O
2
actual value 0.7 %
+
air is increased, 4 optimisation steps already performed
c
small "c" means optimisation in the learning curve for decreasing firing rate
CO
e
50ppm
b- Information on optimisation in the
current firing rate segment
"0"
until now there were no optimi-
sation
"1" ... "31"
linear approach
"32"
optimisation completed
"50" ... "81"
successive repeated control
from the CO
"D 1" ... "D 6"
dynamic test step 1 to step 6
op O
2
trim in standby (during burner start-up), or O
2
trim temporarily switched off as a
function firing rate via parameters 914 and 915.
or O
2
- trim active.
ot
O
2
trim temporarily deactivated (air deficiency, probe dynamics etc).
od O
2
trim deactivated (fault), e.g. test routine failed during burner start-up, dynamic test
negative, O
2
trim temporarily deactivated for over 1 hour etc.
C
Optimisation at increasing firing rate
c
Optimisation at decreasing firing rate