Lamtec ETAMATIC V Quick Reference Download Page 22

21

6   Appendix

Fault 

Code

No.

Restart according to

Description

TRD 

EN676 

600

0

0

Programme check time of sequencer expired.

601

0

0

Leak check fault: gas pressure still applied.

602

0

0

Leak check fault: gas pressure missing.

603

0

0

Vent gas line manually.

605

>88

3

Oil pressure < min !!!

606

1

1

Gas > min appears in oil operation.

608

0

0

Boiler safety chain dropping.

609

1

1

Gas safety chain dropping.

610

>88

3

Oil safety chain dropping.

611

>88

3

Gas pressure too low

612

1

0

Gas pressure too high.

613

0

0

Air pressure signal missing.

616

1

1

Ignition flame goes out in standby operation

617

1

1

Continuous ignition flame goes out under operation

623

0

0

Atomizer switch-ON-pre-period not kept

624

>88

3

Oil pressure too low

625

>88

3

Oil pressure too high

626

>88

3

Atomizer air pressure too low

702

0

0

Flame signal appears during pre-ventilating.

711

0

0

Illegal operating mode change

713

0

0

Incorrect signal combination in operating mode AU

714

0

0

Incorrect signal combination in operating mode BE

715

0

0

Incorrect signal combination in operating mode VO

716

0

0

Incorrect signal combination in operating mode ZP

717

0

0

Incorrect signal combination in operating mode ZU

719

0

0

Fuel valves open too long without flame

720

0

0

Ignition transformer switched on too long

721

0

0

Ignition valve open too long

723

0

0

Ignition process taking too long

724

0

0

Gas valves open when burning oil

725

0

0

Oil valves open when burning gas

726

0

0

Main gas 2 open without main gas 1

727

0

0

Main gas 1 illegally open

728

0

0

Main gas valves and ignition valve open too long

729

0

0

Ignition process taking too long (without pilot burner)

731

0

0

Ignition valve opened without ignition burner

732

0

0

Incorrect signal combination during operation

733

0

0

Incorrect signal combination after operation

734

0

0

Pre-ventilating time not complied with

736

0

0

Leak check: both gas valves open

737

0

0

Seal tightness check: Main Gas 2 delayed for too long at deactivation.

738

0

0

Leak check: main gas 2 missing

739

0

0

Seal tightness check: Main Gas 2 open for too long.

Summary of Contents for ETAMATIC V

Page 1: ...www lamtec de Sensors and Systems for Combustion Engineering Quick Reference for Endusers ETAMATIC V ETAMATIC V S...

Page 2: ......

Page 3: ...to switch the Display 12 4 8 Operation and Display of the O2 Trim 13 4 9 Calling up O2 Trim Text Messages 13 4 10 Displaying the Running Time Meter 13 4 11 Displaying Checksums and Safety Times 14 5...

Page 4: ...regulations DIN EN 298 2012 11 DIN EN 1643 2014 09 DIN EN 13611 2011 12 DIN EN 60730 2 5 2015 10 DIN EN 60730 1 2012 10 2014 35 EU Low Voltage Directive 2014 30 EU EMC Directive 2014 68 EU Pressure E...

Page 5: ...ility of imminent danger If it is not avoided it may result in death or very serious injury The plant including its surroundings could be damaged CAUTION This draws the user s attention to the possibi...

Page 6: ...es of possible actuators Combustion air valve Combustion air blower ETAMATIC VS only Fuel air valve Recirculation valve Up to 20 points usual 11 can be programmed per channel The Display is relative b...

Page 7: ...on high firing rate The integral firing rate controller is built as a PID controller with special functions for combus tion engineering You may use it as a set value controller or controlled by atmosp...

Page 8: ...ted by the 9 p Sub D plug with the ETAMATIC V Use for it the provided lead with the type no 663R0430 The data communication runs via the LAMTEC SYSTEM BUS Alternatively the possibility exists to attac...

Page 9: ...minals for burner firing rate controller and actual value on the relay module type 660R0027 The flue gas damper remains open or the flue gas fan re mains at the highest speed The external burner seque...

Page 10: ...meters Status Firing rate rating Setpoint Actual value feedback Setpoint feedback 2 Dig ital inputs Display change Compound O2 Flame inten sity UEAN Monitoring processor display 1 only if activated in...

Page 11: ...d in the parameter section only available with ETAMATIC V ETAMATIC V S the option Integrated Flame Monitor Customer Interface Using the Keys reset firing rate fault history up firing rate fault histor...

Page 12: ...output of the running time counter and the current time to de termine at which time the fault occurred Red fault LED is on Press key 17 to get STATUS display fault code Press key ENTER Plain text mess...

Page 13: ...he display hides the O2 history automatically after 5 sec O2 trim faults which last for more than 30 sec are stored They are only stored in the EEPROM once the fault is cleared up or the ETAMATIC V le...

Page 14: ...egular operation or Base firing rate operation and then returns automatically to the base setting 4 9 Calling up O2 Trim Text Messages Switch display to O2 trim 4 10 Displaying the Running Time Meter...

Page 15: ...g as soon as the burner is in operation with the relevant curve set flame signal is present 4 11 Displaying Checksums and Safety Times 1st safety time oil in seconds 2nd safety time oil in seconds 1st...

Page 16: ...ia floating contact The burner firing rate controller releases the com bustion internally Combustion is triggered internally by the power control unit 5 3 Range Limits You must set limit values in the...

Page 17: ...f the control unit reaches the shut down range the base firing rate request is emitted If the control unit s setpoint exceed the shut down range a control shut off occurs This is done by internal proc...

Page 18: ...oller 5 8 Meaning of the Display Display in FIRING RATE switch position setpoint actual value regular firing rate input internal firing rate Display in mode MANUAL regular firing rate input via channe...

Page 19: ...TE as BASIC FIRING RATE but ETA MATIC V on SETTING NA POST PURGE AU BURNER OFF no signal present EL SETTING SL CLEAR MEMORY EV SETTING PRE PURGE as PRE PURGE but ETAMATIC V on SETTING ES SETTING CONTR...

Page 20: ...ignal extinguishes during the first safety time 008 0 0 The flame signal extinguishes during the second safety time 009 0 0 Flame signal does not appear during safety time 010 0 0 Flame signal goes ou...

Page 21: ...ratio control blocked channel 4 320 1 1 Broken wire at correction input 321 1 1 Broken wire at feedback channel 1 322 1 1 Broken wire at feedback channel 2 323 1 1 Broken wire at feedback channel 3 3...

Page 22: ...g mode AU 714 0 0 Incorrect signal combination in operating mode BE 715 0 0 Incorrect signal combination in operating mode VO 716 0 0 Incorrect signal combination in operating mode ZP 717 0 0 Incorrec...

Page 23: ...o 889 0 0 Time interval between remote fault resets is too short 904 1 1 Error in reference of firing rate 911 1 1 Error in reference channel 1 912 1 1 Error in reference channel 2 913 1 1 Error in re...

Page 24: ...23 6 Appendix 6 3 Calling Up the Condition of the Digital Inputs Meaning of the digital inputs of the ETAMATIC V Switch to digital inputs with keys 16 and 17 Signal applies Signal does not apply...

Page 25: ...according to IEC 60127 2 Sheet 5 1500A 250VAC Melting Integral I t 40 A s e g Littelfuse 0215002 M XP Fuses that fulfill these requirements are ceramic tube fuses with the marking T2AH 250V Fig 6 3 B...

Page 26: ...25 6 Appendix 6 5 EU Declaration of Conformity...

Page 27: ...26 6 Appendix...

Page 28: ...27 6 Appendix...

Page 29: ...28 6 Appendix...

Page 30: ...KG Wiesenstra e 6 D 69190 Walldorf Telefon 49 0 6227 6052 0 Telefax 49 0 6227 6052 57 info lamtec de www lamtec de Publication no DLT2004 20 aEN 022 The information in this publication is subject to t...

Reviews: