- 31-
P29
Coil temperature to active defrost
-8~5
℃
0
0
0
0
P30
Coil temperature to stop defrost
5~30
℃
20
20
20
20
P31
The max defrost time
2~20min
15
15
15
15
P32
EEV control mode
0-no 1-Checking table 2-manual 3-
suction superheat 4-Discharge superheat
4
4
4
4
P33
EEV manually initial open steps (heating)
50~480(Only valid when P32=2)
400
400
400
400
P34
EEV manually initial open steps (cooling)
50~480(Only valid when P32=2)
400
400
400
400
P35
In DHW mode, highest water temperature for
compressor running
0~60
℃
55
55
55
55
P36
Time interval between compressor and E1
startup (reserved)
0~999min
0
0
0
0
P37
Temperature difference for adjustable DC fan
speed (heating)
2~15
℃
6
6
6
6
P38
Temperature difference for adjustable DC fan
speed (cooling)
3~18
℃
8
8
8
8
P39
Choose compressor model (reserved)
0~999
258
258
258
258
P40
Compressor frequency setting
0- Manual 1-Auto
1
1
1
1
P41
Compressor oil return frequency
10~100 Hz ( When P40=0 )
50
50
50
50
P42
Compressor frequency limiting current
1~50A
0
0
0
0
P43
Compressor frequency reduction current
1~50A
0
0
0
0
P44
Compressor shutdown current
1~50A
0
0
0
0
P45
Maximum running frequency
50~120 Hz
70
85
85
70
P46
Minimum running frequency
0~90 Hz
25
25
25
25
P47
Defrost running frequency
30~90 Hz
65
65
65
65
P48
DHW maximum frequency
2~10 (Max frequency X 20~100%)
10
10
10
10
P49
Discharge superheat percentage coefficient
0~99 (display value multiply 0.1)
2
2
2
2
P50
Discharge superheat differential coefficient
0~99
1
1
1
1
P51
High pressure value to limit compressor
frequency rising
2.0~4.5MPa (display value multiply 0.1)
43
43
43
43
P52
High pressure value to cancel compressor
frequency limit
2.0~4.5MPa (display value multiply 0.1)
39
39
39
39
P53
Protection pressure (High)
2.5~5.0MPa (display value multiply 0.1)
45
45
45
45
P54
Protection pressure (Low)
0.01~1.0MPa (display value multiply 0.01)
10
10
10
10
P55
High pressure protection recovery pressure
difference
0.2~1.5MPa (display value multiply 0.1)
5
5
5
5
P56
Low pressure protection recovery Pressure
difference
0.01~1.0MPa (display value multiply 0.01)
15
15
15
15
P57
Discharge protection temperature
110~125
℃
115
115
115
115
P58
Temperature differential for Adjustable water
pump 1 speed
3~8
℃
5
5
5
5
P59
PWM water pump minimum running speed
2~8 (stands for 20% to 80% of the speed)
8
8
8
8
P60
DC motor maximum running speed
500-1500RPM ( display value multiply 10)
70
85
90
85
P61
minimum water flow
3~80L/min, Step 1
14
16
18
22
P62
Definition of A/C function
0-C heating 1-Only cooling 2-Only
Heating
0
0
0
0
P63
DHW validation
0
–No 1- Yes.
1
1
1
1
P64
EEV minimum open step
0-480
70
70
70
70
P65
Function definition for water pump C2
0-Auxiliary pump, 1- Indoor circulating
pump
0
0
0
0
P66
Selected heat source
0- Air source.
1- Water source
(
Reserved
)
0
0
0
0
P67
Room thermostat (reserved)
0- OFF , 1- ON
0
0
0
0
P68
Flow switch selection
0-Water flow switch, 1-Water flow sensor
1
1
1
1
P69
Fan motor type
0-AC motor 1-First DC motor 2-
Second DC motor. 3-Two DC motor
1
1
1
3
P70
Auto restart
0-OFF, 1-ON
1
1
1
1
P71
DC motor speed control
0- Manual, 1- Auto
1
1
1
1
P72
DC motor fixed speed
0-1500rpm (display value multiply 10)
0
0
0
0
P73
Pressure controller type
0-Pressure sensor 1-Pressure switch
0
0
0
0
P74
EVI EEV control mode
0-no 1-checking 2- manual 3-auto
3
3
3
3
P75
EVI EEV manually initial open steps(heating)
40~480
40
40
40
40
Summary of Contents for FSH HP KING 12DC32
Page 1: ... 1 DC INVERTER MULTIFUNCTIONAL AIR TO WATER HEAT PUMP User Manual Model KING HEAT 6 9 12 18 ...
Page 14: ... 14 D 3X6 9 12 18 Installation Space Heating Cooling DHW ...
Page 15: ... 15 Solar Application 1 Solar Application 2 ...
Page 18: ... 18 4 4 1 System Diagram A P90 1 P65 1 B P90 0 P65 0 ...
Page 19: ... 19 4 4 2 Wiring Diagram KING HEAT 6 9 12 ...
Page 20: ... 20 KING HEAT 18 ...
Page 39: ... 39 6 2 System Drawing ...