9. 

Modbus-protocol

The Lambrecht meteo Modbus sensors and the met[LOG] follow the specifi cation of the Modbus organization: "MODBUS 
APPLICATION PROTOCOL SPECIFICATION V1.1b3". (See www.modbus.org).

9.1 

Data encoding 

MODBUS uses the "big-endian" format for addresses and data. This means that if a value is transmit-ted with a number 
format that is larger than a single byte, the "most signifi cant byte" is sent fi rst. For values that go beyond one register (e.g. 
32 bit) this is not clearly specifi ed for the Modbus. In these cases (32 bit or 64 bit) the LAMBRECHT Modbus sensors follow 
the big-endian number format.

Example Big-Endian:

Register size value 
16 - bits 0x1234 is transmitted in the order: 0x12 0x34.

Example Big-Endian (32 bit or 64 bit):

Register size value 
32 - bits 0x12345678 is transmitted in the order: 0x12 0x34 0x56 0x78.

9.2 

Device-address

The addresses 1...247 are permitted for Modbus.

9.3 

Standard confi guration - Default

Baud rate: 

19200 Baud

Address: 

Each sensor type (or family) has its own default address. 

Default addresses of the LAMBRECHT sensors:

Address Sensor

1 Wind speed
2 Wind direction
3 Precipitation rain[e]
4 THP
5 EOLOS IND
6 com[b]
7 PREOS
8 ARCO
9 u[sonic]

10 Pyranometer 2nd Class

11  Secondary standard Pyranometer / First Class Pyranometer

12 PT100 to Modbus converter (temperature)

Byte frame according to MODBUS standard for RTU mode: 
8E1 (1 start bit, 8 data bits, 1 parity bit (even parity), 1 stop bit)

9.4 

Modbus command set

The LAMBRECHT Modbus sensors support the following commands:
•  Read Input Register" command:   

0x04 (measured data)

•  Write Multiple Register" command: 

0x10 (Write sensor data)

6

Summary of Contents for INDUSTRY Modbus

Page 1: ...good starting values large measuring and temperature application ranges easy mast mounting optimal heating concept Content 1 Initial operation 2 Principles of installation 3 Setting up the North Dire...

Page 2: ...lower edge of the upper wind speed sensor is 0 1 to 0 5 m above the upper edge of the lower wind direction sensor 2 Principles of installation Attention Because the installation takes place in a dang...

Page 3: ...measurements the north mark on the sen sor must be aligned with the geographical north direction You have to turn the marking exactly over the marking at the sensor shaft When you have aligned the mar...

Page 4: ...14567 14577 INDUSTRY Modbus Manual Wind Sensors INDUSTRY Modbus Manual 14567 14577 INDUSTRY Modbus Manual 7 Wiring diagram 4...

Page 5: ...Manual Wind Sensors INDUSTRY Modbus 14567 14577 INDUSTRY Modbus Manual 8 Dimensioned drawings Accessories optional 14567 U6 Mast adapter Id No 32 14567 006 000 5...

Page 6: ...s 0x1234 is transmitted in the order 0x12 0x34 Example Big Endian 32 bit or 64 bit Register size value 32 bits 0x12345678 is transmitted in the order 0x12 0x34 0x56 0x78 9 2 Device address The address...

Page 7: ...al place INT 30202 Wind direction average value since last retrieval 10 1 decimal place INT 30203 Wind direction maximum value 10 1 decimal place INT 30204 Wind direction minimum value 10 1 decimal pl...

Page 8: ...perature If the autocon guration is started with the data logger met LOG it queries the available mapping registers on each COM interface in the device address range 1 25 For this purpose the number o...

Page 9: ...Endian WORD 31592 Global radiation instantaneous values Low WORD uncompensated 0x04 Big Endian WORD 9 8 1 Mapping register INDUSTRY Modbus Register address Register value Unit Factor Description 4600...

Page 10: ...0 7 50 m s Accuracy 2 0 5 m s at 0 7 5 m s and 2 FS at 5 02 50 m s Resolution 1 0 02 m s Starting value 0 7 m s 0 7 m s Interface RS485 RS485 Protocol Modbus RTU Modbus RTU Weight 0 35 kg 0 25 kg Mea...

Reviews: