Wind Sensors EFFICIENT Modbus (14579)

(14579) EFFICIENT Modbus

Manual

9.5 

Instantaneous values / realtime values (Input Register)

The following measured values are provided:

Register address Parameter name

Unit

Divisor

Quantity of registers

Access type

30001

Wind speed

m/s

10

1

Read only

30201

Wind direction

°

10

1

Read only

Example:

 Retrieve wind speed

0D 04 75 31 00 01 7A

C5

0D 04 02

00

1F

E8 F9

LEN 

6

Transmission 

Query =>

Source 

Master

Dest 

Slave 13

Function 

Read Input Register (4)

Func Desk 

Address=30001, Quantity of Register=1

Checksum 

OK:C57A

LEN 

5

Transmission 

Response <=

Source 

Slave 13

Dest 

Master

Function 

Read Input Register (4)

Func Desk 

Byte count=2

Data 

00 1F

Checksum 

OK:F9E8

9.6 

Period data - Average, maximum and minimum (Input Register)

Register

Parameter name 

Unit 

Divisor

Quantity of registers Access type

30002 

Wind speed average

m/s 

10

1

Read only 

30003 

Wind speed maximum

m/s 

10

1

Read only 

30004 

Wind speed minimum

m/s 

10

1

Read only 

30202 

Wind direction average

° 

10

1

Read only 

30203 

Wind direction maximum

° 

10

1

Read only

30204 

Wind direction minimum

° 

10

1

Read only

The data are valid for the period between the current request and the previous request. The maximum range of a period is 

1 hour. Recalling the average value of a minimum, maximum and average group will erase the appropriate registers. 
Retrieve the values of a group in the sequence minimum, maximum, average.
Use command: 0x03

Example

: Retrieve wind speed (min. max. avr.) and erase the register content

01 04 75 34 00 01 6A 08 01 04 02

00 00

B9 30 01

04 75 33 00 01 DB

C9

01 04 02

00 D6

38 AE 01 04

75 32 00 01 8A 09 01 04 02

00

14

B9 3F

LEN 

6

Transmission 

Query =>

Source 

Master

Dest 

Slave 1 

Function 

Read Input Register (4)

Func Desk 

Address=30004, Quantity of Register=1

Checksum 

OK:86A

LEN 

5

Transmission 

Response <=

Source 

Slave 1

Dest 

Master

Function 

Read Input Register (4)

Func Desk 

Byte count=2

Data

 

00 00

Checksum 

OK:30B9

LEN 

6

Transmission 

Query =>

Source 

Master

Dest 

Slave 1

Function 

Read Input Register (4)

Func Desk 

Address=30003, Quantity of Register=1

Checksum 

OK:C9DB

LEN 

5

Transmission 

Response <=

Source 

Slave 1

Dest 

Master

Function 

Read Input Register (4)

Func Desk 

Byte count=2

Data

 

00 D6

Checksum 

OK:AE38

LEN 

6

Transmission 

Query =>

Source 

Master

Dest 

Slave 1

Function 

Read Input Register (4)

Func Desk 

Address=30002, Quantity of Register=1

Checksum 

OK:98A

LEN 

5

Transmission 

Response <=

Source 

Slave 1

Dest 

Master

Function 

Read Input Register (4)

Func Desk 

Byte count=2

Data

 

00 14

Checksum 

OK:3FB9

8

Summary of Contents for EFFICIENT Modbus

Page 1: ...or concept high quality materials meet func tional design EFFICIENT sensors also impress with their high accuracy effortlessly simple mounting principles and corrosion resistant materials EFFICIENT se...

Page 2: ...t a certified disposal company for electronic waste Outside the EU Please follow the regulations in your country regarding the appropriate disposal of waste electronic equipment Content 1 Initial oper...

Page 3: ...the upper wind speed sensor is 0 1 to 0 5 m above the upper edge of the lower wind direction sensor 2 Principles of installation Because the installation takes place in a danger ous height the assembl...

Page 4: ...s the North mark on the sen sor must be aligned with the geographical north direction You have to turn the marking exactly over the marking at the sensor shaft When you have aligned the marks you may...

Page 5: ...Manual Wind Sensors EFFICIENT Modbus 14579 14579 EFFICIENT Modbus Manual 7 Wiring diagram 5...

Page 6: ...Manual Wind Sensors EFFICIENT Modbus 14579 14579 EFFICIENT Modbus Manual 8 Dimensional drawings Accessories optional 14567 U6 Mast adapter Id No 32 14567 006 000 6 3 10 mm...

Page 7: ...or Values of 9999 indicate an internal sensor error 9 3 Standard configuration Default Baud rate 19200 Baud Byte frame 8E1 1 start bit 8 data bits 1 parity bit even parity 1 stop bit RTU Sensor addres...

Page 8: ...ent request and the previous request The maximum range of a period is 1 hour Recalling the average value of a minimum maximum and average group will erase the appropriate registers Retrieve the values...

Page 9: ...egister 8 Checksum OK 8BCA LEN 19 Transmission Response Source Slave 13 Dest Master Function Read Holding Register 3 Func Desk Byte count 16 Data 30 30 2E 31 36 34 38 30 2E 30 30 31 31 33 30 00 Checks...

Page 10: ...stics Measuring ranges 0 360 0 7 50 m s Accuracy 2 0 5 m s at 0 7 5 m s and 2 FS at 5 02 50 m s Resolution 1 0 02 m s Starting value 0 7 m s 0 7 m s Interface RS485 RS485 Protocol Modbus RTU Modbus RT...

Reviews: