3.3 TECHNICAL CHARACTERISTICS
3.3.1 Technical characteristics of the Connect CRP
Dimensions (LxWxH)
133 mm x 95.5 mm x 26.5 mm
Protection rating
IP 40
Power supply
24Vdc ± 5%; max 2W
Relay
SPST-NO (normally open and voltage-free contact)
Maximum capacity: 5A 250Vac / 5A 30Vdc
Adjustment range
Heating
5°C – 30°C
Cooling
5°C – 30°C
DHW
30°C – 60°C
Temperature sensor
Internal sensor with accuracy < 1.0 °C
Display resolution 0.1°C
WIFI module
2.4GHz frequency, 802.11 b/g/n protocol
RF module
868MHz frequency, 2-GFSK modulation
Operating conditions
Operating temperature 0÷50 °C, Max. relative air humidity 70 % @ 50°C (non-condensing), Storage
temperature -20 ÷70 °C
Standards
2014/35/EU Low voltage directive (LVD)
2014/30/EU Electromagnetic compatibility directive (EMC)
2014/53/EU Radio Equipment Directive (RED)
3.3.2 Power supply technical characteristics
Input voltage
220-240 Vac, 44 mA, 50-60Hz
Output voltage
24 Vdc, 180 mA, 4.2 W
4. THE CONNECT CRP DEVICE
4.1 DESCRIPTION OF BUTTONS
Symbol
Function
Select/Confirm button
Exit or return to previous menu
Move the selection between the various menus
Increase or decrease the selected parameter value
4.2 FIRST CONFIGURATION
NOTE
BEFORE CONFIGURING THE Connect CRP DEVICE, DISABLE THE UNIT'S CLIMATIC CURVES
TO AVOID INCORRECT FUNCTIONING OF THE CURVES MANAGED BY THE Connect CRP
When the device is switched on for the first time, or following a reset to the factory values via the TECHNICAL menu,
a guided procedure for configuring the system is proposed.
However, all the selections made can also be changed at a later time by accessing the relevant menus.
Summary of Contents for Connect CRP
Page 2: ......
Page 229: ...229 EL cod 3542B390 Rev 00 06 2022 2 2 3 7 7 3 8 modbus RS485 0 34 mm2 0 5 mm2 25 m 4 5 9...
Page 230: ...230 EL cod 3542B390 Rev 00 06 2022 3 1 230Vac L1 N 10 3 2 Connect CRP 5A 250Vac Connect CRP 11...
Page 303: ...303 SR cod 3542B390 Rev 00 06 2022 2 2 3 7 7 3 8 modbus RS485 0 34 mm2 0 5 mm2 25 m 4 5 9...
Page 304: ...304 SR cod 3542B390 Rev 00 06 2022 3 1 230Vac L1 N 10 3 2 Connect CRP 5A 250Vac Connect CRP 11...
Page 373: ......
Page 374: ......
Page 375: ......