1.5
Wiring
the
UPS
WARNING:
All electrical wiring must be performed by qualified electrician or trained personnel. Make
sure the line power is off. Switch off all input and output circuit breakers on the UPS unit before making
any electrical connections.
1.5.1 Wiring the PTS to the UPS
Wire the PTS to the UPS according to the schematic shown in Figure 5.
1. The PTS is pre-wired with 2 cables marked as
“
UPS
IN”
and
“
UPS
OUT”
. Connect these cables from PTS to the
respective connectors on the UPS.
2. Connect the AC input wires to the AC input terminal blocks on the PTS. Ensure proper polarity (Line, Neutral
and Ground to the respective terminal).
3. Connect AC output wires to the AC output terminal blocks on the PTS. Ensure proper polarity (Line, Neutral
and Ground to the respective terminal).
Figure 5: Wiring the PTS to the UPS
1.5.2 Sensor cable wiring to the UPS
1. Connect the temperature sensor to the UPS unit (Battery Temperature connector
). The other end is
connected to the batteries later in the procedure.
2. Refer to Figure 1 & 2, connect the following ports if used.
•
USB Connector
.
•
RS-232 Connector
.
•
Dry contacts
.
•
Program input
.
•
External FAN Connector
.