Laing SM-303-B Installation & Operating Manual Download Page 6

7

System Maintenance

Standard Dry Run Thermostat Operation

Each SM(T)-303 and UC(T)-303 model pump has a built-in 200ºF thermal cut-off in order to protect 
against overheating, which could cause damage to the pump motor.  In the event that disruption of your 
immediate hot water supply is noticed it is possible that the pump has or is running dry and the internal 
dry run thermal protector has shut down the pump motor. In this event, it is important that the dry run 
condition be corrected (otherwise the pump will fail prematurely) by following the procedure below:
1.  Disconnect power to the pump motor.
2.  Close the shut-off valves on each side of the pump.
3.  Remove the pump motor/rotor assembly from the pump housing.
4.  Dry off the pump motor/rotor assembly. Remove the rotor and check for any calcium build-up, 
foreign matter or any signs of wear. If these signs are not present, put the rotor back in place on the 
ceramic ball.
5.  Hold the pump motor/rotor assembly upright and plug in the unit for about 10 seconds to see if the 
rotor spins evenly and quietly. If the motor does not go on, allow a few more minutes for the thermo

-

stat to reset as the unit cools down.
6. If the rotor spins properly, unplug the motor and reinstall the assembly into the pump housing.
7.  Turn both shut-off valves to the on position, reconnect the electrical supply to the pump motor, and 
be sure that air is properly purged from your system.

130ºF On-Off Thermostat Option “C”

Pumps with the letter “C” in the model are provided with a factory option “C” internal thermal cut-off which 
automatically shuts the pump down when the temperature of the water passing through the pump housing 
reaches 130ºF +/- 10ºF and turns the pump on at 110ºF +/- 10ºF (SM/SMT 909-14 only).

Variable Setting On-Off Thermostat Option “R”

Pumps with the letter “R” in the model designation are provided with a factory installed internal 
thermal cut-off with an adjustable On-Off temperature dial located on the outside of the motor.  This 
dial can be rotated by placing a thin screw driver in the dial slot which allows the pump to turn off 
automatically when the water temperature passing through the pump housing reaches the dial setting 
selected-between 95ºF and 140ºF.  The pump will turn back on automatically when the water tem

-

perature cools down to 10ºF below the set temperature (SM/SMT-303 only).

•  Do not attempt to lubricate 

the pump. The pump is self-

lubricating.

•  Prevent the pump from run-

ning dry.

•  Flush the system of any de

-

bris and re-purge all air from 

the system in the event of any 
water supply interruptions in 

plumbing line.

•  Prevent heavy scale build-up 

by keeping the hot water 
temperature 140ºF or less.

•  Don’t over salt your water 

 

conditioner.

Replacement Parts

Please provide the following 

information 

when ordering:
• Model number
• Serial number
• Part description

6

Do 

•  install an air vent mounted in a vertical position (if provided).
•  use 1/2” recirculation line tubing.
•  check to be sure there are no crimps or sharp bends in the recirculation line that would restrict the flow.
•  be sure the check valve is installed in the proper direction of the flow.
•  be sure all air is purged from the system prior to starting the pump.
•  use a water conditioner if you have hard water.
•  be sure the gate valves are open before turning on the pump.
•  install the pump pumping in upward direction only.

Do Not

•  use grease or oil to lubricate the pump - it is self-lubricating.
•  over tighten the screw ring (SM-303 models).
•  install the pump with the motor above the pump housing.
•  install the pump pumping away from the water heater nor pumping downward.
•  start the pump before the system is full of water and purged of air.
•  allow the water heater temperature above 140ºF.

•  install the pump in the supply line to faucets.

•  use any pipe size other than 1/2” for SM-303 or UC-303 models.

•  position the pump at the top of the water heater.

Notes:
Keep The Hot Water Temperature Below 140ºF: 

Higher temperatures can cause calcium and mag

-

nesium elements to come out of solution and create solids which could not only cause damage to the 
pump but also reduce water heater efficiency and premature failure of the water heater.

Hard Water Conditions: 

Use a water conditioner. Hard water can cause scale build-up and eventually 

reduce the life of the pump and other system components.

If timer controlled operation is desired, the timer may be programmed to allow the Autocirc 
to operate during the hours desired (i.e. “ON” from 7:00 a.m. to 9:00 p.m. and “OFF” from 
9:00 p.m. to 7:00 a.m.) as follows:

•  Open timer cover and rotate the dial clockwise until the cor

-

rect time is aligned with the pointer (

) on the right side (3 

o’clock position) of the dial.  A timer instruction label affixed to 
the right side of the timer housing also shows this time setting 

point.

•  Automatic Operation: PULL the tabs Upward on timer for the 

desired operating period of time.  Example: If the desired 
operating time is 7:00 a.m. to 9:00 a.m., all  tabs should be 
Pulled out between 7 and 9. NOTE: The timer may be set for 
multiple operating periods of time.

•  Slide the switch bar to “timer”.

The timer mode will provide the most cost effective method of operation and can be pro

-

grammed to run only during the time periods when hot water is most frequently required.  
Even during controlled timer operation, the Autocirc will only turn on when the built-in 
thermostat senses that additional hot water is required at the point of installation.

Protected by one or more of the following Patents:

4580335, 4615662, 4822256, 4834628,  

5094593, 5143049, 5749715, 6149407, 6227235

Do’s and Do Not’s

Timer Controlled Operation

SM-303-B

SM-909-B-14

Housing

“O” Ring

Rotor

Assembly

Motor

Assembly

Screw

Ring

UC-303-B

Housing

“O” Ring

Rotor

Assembly

Motor

Assembly

Screw

Ring

30 Min. Tabs

Summary of Contents for SM-303-B

Page 1: ...mmediately after the pump is turned off During normal operation an occasional air bubble may pass through the pump housing causing a momentary gurgling noise However if noise at the pump persists for any prolonged period correct the problem see below The check valve is mistakenly installed on the inlet side of pump or in the wrong direction The inlet side shut off valve is closed or clogged There ...

Page 2: ...ufficient to overcome the friction losses created by the piping in the house water sup ply line and the return line Oversized Pumps Pumps should not be so large as to produce flow rates that may eventually erode holes in the pipes According to the Copper Development Association excessive erosion occurs at a velocity of about 5 ft per second and higher or about 4 GPM in 1 2 Type M copper pipe and 8...

Page 3: ...ufficient to overcome the friction losses created by the piping in the house water sup ply line and the return line Oversized Pumps Pumps should not be so large as to produce flow rates that may eventually erode holes in the pipes According to the Copper Development Association excessive erosion occurs at a velocity of about 5 ft per second and higher or about 4 GPM in 1 2 Type M copper pipe and 8...

Page 4: ...e drain valve 6 Connect the return line at the last faucet riser and run to the water heater Tee the return line as close to the end of the hot water supply line as possible and run the return line back to the water heater 7 Install the pump and other compo nents required in accordance with the diagrams provided in fig 1 or 2 and con nect the return line to the water heater also see fig 3 For SM T...

Page 5: ...e drain valve 6 Connect the return line at the last faucet riser and run to the water heater Tee the return line as close to the end of the hot water supply line as possible and run the return line back to the water heater 7 Install the pump and other compo nents required in accordance with the diagrams provided in fig 1 or 2 and con nect the return line to the water heater also see fig 3 For SM T...

Page 6: ...when ordering Model number Serial number Part description 6 Do install an air vent mounted in a vertical position if provided use 1 2 recirculation line tubing check to be sure there are no crimps or sharp bends in the recirculation line that would restrict the flow be sure the check valve is installed in the proper direction of the flow be sure all air is purged from the system prior to starting ...

Page 7: ...when ordering Model number Serial number Part description 6 Do install an air vent mounted in a vertical position if provided use 1 2 recirculation line tubing check to be sure there are no crimps or sharp bends in the recirculation line that would restrict the flow be sure the check valve is installed in the proper direction of the flow be sure all air is purged from the system prior to starting ...

Page 8: ...ng noise immediately after the pump is turned off During normal operation an occasional air bubble may pass through the pump housing causing a momentary gurgling noise However if noise at the pump persists for any prolonged period correct the problem see below The check valve is mistakenly installed on the inlet side of pump or in the wrong direction The inlet side shut off valve is closed or clog...

Reviews: