48
| HPI Combi Flow User Guide |
Version 3.11
www.lafert.com
Par.
Name
Minimum
Maximum
Default
Units
P5-14
Fieldbus PDI-3 Function Select
0
2
0
-
When using an optional Fieldbus interface, this parameter configures the parameter source for the 3rd process data word transferred
from the network master to the drive during cyclic communications:
0 : Not used.
No function.
1 : User Reference.
0 to 1000 = 0% to 100.0%.
2 : User Register 3.
Can be accessed by PLC program or group 9 parameters.
P5-15
Modbus Response Delay
0
16
0
Chr
Allows the user to configure an additional delay between the drive receiving a request via the Modbus RTU interface, and transmitting a
reply. The value entered represents the delay in addition to the minimum delay permissible according to the Modbus RTU specification,
and is expressed as the number of additional characters.
P5-16
Drive Modbus Address
0
247
0
-
The drive Modbus (and Optibus) address is set in P5-01 which has a maximum value of 63. If a higher Modbus address is required for a
larger network, it can be set in this parameter.
If this parameter is set to a value greater than 0, this address will become the Drive Modbus address. If this value is set to 0, P5-01
determines the Drive Modbus address.
9.5. Advanced Parameters
For Advanced Parameters, basic information only is provided in this guide. The parameter functions are described more fully in HP
Drive Tools Studio PC software.
9.5.1. Parameter Group 6 – Advanced Configuration
Par.
Function
Setting Range
Default
Notes
P6-01
Firmware Upgrade Enable
0
Disabled
0
This parameter should not be
adjusted by the user.
1
Update I/O & P/S
2
Update I/O
3
Update P/S
P6-02
Thermal Overload Management
4 – 32kHz (Model Dependent)
Motor Rating
Dependent
Minimum Effective Switching
Frequency.
P6-03
Auto Reset Time Delay
1 – 60 Seconds
20s
P6-04
Relay Output Hysteresis
0.0 – 25.0%
0.3%
P6-08
Max Speed Reference Frequency
0 – 20kHz
0 kHz
P6-10
Function Block Program Enable
0
Disabled
0
1
Enabled
P6-11
Speed Hold Time on Enable
0 – 600s
0s
P6-12
Speed Hold / DC Injection Time on Disable
0 – 250s
0s
P6-18
DC Injection Current
0.0 – 100.0%
0.0%
P6-22
Reset Fan Run Time
0
No Reset
0
1
Reset
P6-23
Reset Energy Meters
0
No Reset
0
1
Reset
P6-24
Maintenance Time Interval
0 – 60000 Hours
0 Hours
P6-25
Reset Maintenance Indicator
0
No Reset
0
1
Reset
P6-26
Analog Output 1 Scaling
0.0 – 500.0%
100.0%
P6-27
Analog Output 1 Offset
-500.0 – 500.0%
0.0%
P6-28
P0-80 Display Index
0 - 200
0
P6-29
User Default Parameters
0
No Function
0
1
Save user parameters
2
Clear user parameters
P6-30
Level 3 (Advanced) Access Code
0 – 9999
201
9
Extended P
arameters