3. DISPLAYS

For approx. three seconds upon switching on, the instrument displays  

(internal self-test phase). Subsequent indications depend

on the operating status of the regulator. TABLE 2 gives the indications associated with the various states.
The temperature measured by the sensor is processed by the microprocessor to display it in the most representative way. For this
purpose it may be corrected with a fixed offset, assigning the parameter 

OS1

a value other than zero, and displayed in the desired

scale by setting the parameter 

SCL

: with 

SCL=1°C

the temperature is displayed in the Celsius scale with auto-range 0.1°/1°C;

with 

SCL=2°C 

or 

°F

the temperature is displayed with a resolution of a degree in the Celsius or Fahrenheit scale respectively.

Prior to display, the temperature is processed by a special algorithm, which allows the simulation of a thermal mass directly
proportional to the 

SIM

value; the resulting effect is a reduction in the oscillation of the displayed value. 

The output status is shown through the luminous point on the display.

CAUTION

: when changing the display scale SCL, the parameters related to the absolute (SPL, SPH, 1SP) and differential (1HY,

1PB, OS1) temperatures MUST be reconfigured.

TABLE 2

4. OPERATION DESCRIPTION

4.1. C

ONTROLLER STANDBY

. Parameter BAU determine the functions associated with the button 

: with 

BAU=NON

the button

is used to exit from the setup or to abort the autotuning routine; with 

BAU=SBY

the button has an additional function, i.e. it can

also be used to switch on and off the controller: keeping this button pressed for about 3 seconds changes the controller status (on
/ stand-by). When it’s on standby, the controller shows OFF, the output is off and it’s not possible to have access to the parameter
setup.

4.2. T

YPE OF CONTROL

. The output may operate in the ON/OFF or PID mode: 

1Y=HY

is fixed for ON/OFF control, 

1Y=PID

for PID control.

4.3. ON/OFF 

CONTROL

. In the ON/OFF mode the output is ON or OFF in

relation to the input temperature, set point 

(1SP)

and hysteresis value 

(1HY)

. The

hysteresis indicates the amplitude of deviation of the temperature from the set point
in order to reactivate the output. Increasing the hysteresis value decreases the
switcheovers of the output, while decreasing the hysteresis value gives finer control.
For the output to operate in the heating mode, assign a negative value (see Figure
1) to 

1HY

; assign a positive value for control in the cooling mode (see Figure 2).

With 

1HY=0

the output is permanently cut out. After a switchover the output

remains in the new state for a minimum time of 

1CT

seconds irrespective of the

temperature value.

4.4. PID 

CONTROL

. In the PID mode the output is ON for a fraction of the cycle

time 

1CT

. The cycle time characterises the dynamics of the system to be controlled

and influences the accuracy of the control: the higher the system speed of response
the shorter the cycle time to obtain greater temperature stability and less sensitivity
to variations in load. Assign a negative value to 

1PB

to make the output operate in

the heating mode (see Figure 3) and a positive value for control in the cooling mode.
With 

1PB=0

the output is permanently cut out.

INSTRUCTIONS FOR INSTALLATION AND USE.

---

Internal self-test (3 seconds)

E1

In tuning: timeout 1error

5.4

Sensor T1 temperature

E2

In tuning: timeout 2 error

or

Over range or breakage T1

E3

In tuning: over range error

Tun / 5.4

Instrument in auto-tuning

OFF

Controller standby

Summary of Contents for LTR15

Page 1: ...ing its configuration parameters from the setup menu The instrument comes with a general setup and cannot therefore be used without having first checked that the parameters are correct Setup is accessed by pressing in succession the keys and keeping them pressed simultaneously for 3 seconds The available parameters appear in TABLE 1 shown below Use the button to pass from one parameter to the next...

Page 2: ...atus on stand by When it s on standby the controller shows OFF the output is off and it s not possible to have access to the parameter setup 4 2 TYPE OF CONTROL The output may operate in the ON OFF or PID mode 1Y HY is fixed for ON OFF control 1Y PID for PID control 4 3 ON OFF CONTROL In the ON OFF mode the output is ON or OFF in relation to the input temperature set point 1SP and hysteresis value...

Page 3: ... extremely sensitive to small temperature variations and can make the system instable With 1DT 0 the derivative control is disabled 4 5 MALFUNCTIONING Following a sensor malfunction appears on the display and the output is controlled according to the value of the parameter 1PF CAUTION when programming the hysteresis 1HY or the proportional band 1PB it is advisable to consider the number of switcho...

Page 4: ...derivative action time 1Dt caution a high value makes the system sensitive to small variations and may be a source of instability CAUTION during the auto tuning procedure the temperature oscillates near the set point it is therefore advisable to remove products to be controlled within severe specifications 6 RECALIBRATION If it is necessary to recalibrate the instrument for example following repla...

Page 5: ...NS FOR INSTALLATION AND USE VIA PADOVA 25 31046 ODERZO TV ITALY TEL 0422 815320 815303 TELEFAX 0422 814073 www lae electronic com E mail info lae electronic com PARTNER VENEZIA 041 5460713 LTR15A1RE BG LTR15C1FE BG LTR15T1RE BG ...

Reviews: