LAE electronic CDC122T1R2 Instructions For Installation And Use Download Page 3

When probe T2 is faulty, any new defrost is inhibited.

7. EVAPORATOR FAN CONTROL

7.1 R

UN WITH

T

HERMOSTAT

.

During temperature control, the fans can work in three different ways. If 

Fct

=

-01

, the fans work continuously. If 

Fct

=

00

,

the fans are stopped simultaneously with the cooler. If 

Fct

is set between 

1

and 

10

minutes, after the cooler has stopped, the fans continue to run for

the programmed amount of minutes. In both latter two cases, the fans are switched on simultaneously with the cooler.

7.2 R

UN DURING AND AFTER

D

EFROST

.

During and immediately after defrost, the fans are controlled by parameters 

Fid

and 

FrS

. If 

Fid=00

, at the

start and all through defrost the fans are off; they are switched on again, after compressor re-start, when the evaporator probe T2 matches the 

FrS

temperature. If 

Fid=01

; in this case the fans are active as long as the evaporator has a temperature lower than 

FrS

. If 

Fid=02

; all through defrost

the fans are on (even with 

dty=ELE

or 

GAS

).

8. ALARM FUNCTION AND PROBE FAILURE

A check on the correct refrigeration plant function is performed by monitoring temperature T1, T2 or T3, selectable via 

Ain

parameter. 

ALo

and 

Ahi

determine, respectively, the lower and higher temperature alarm threshold.

AdL

allows the control of the alarm function: with 

-01

the temperature alarm is excluded, while, if this parameter is 

00

, the alarm output is on

immediately when the condition is detected. If 

AdL

is programmed between 

01

and 

120

minutes, the temperature must constantly remain over the

alarm threshold for the chosen time before the signallings take place.
When the alarm starts, “ALM” blinks on the display, alarm relay  and buzzer are switched on. The signallings remain, 

even when the alarm

condition is over

, until the alarm is "acknowledged" by pressing any key. Now, if the temperature is within the alarm limits, any alarm indication

disappears. Otherwise the current temperature is displayed alternating with “ALM”, the relay is always on and, for 1 min. every 30, the buzzer beeps;
all this happens as long as the alarm condition persists.
As a result of failure or overrange of one of the probes, the display shows either “PF1” or “PF2”, the alarm output is switched on immediately. Also
in this case the condition must be acknowledged by pressing any key.
The alarm output contact is also closed when the instrument is powerless.

During defrost and dripping, the high alarm monitoring is inhibited.

9. PROBE RE-CALIBRATION

Should it be necessary to recalibrate the unit, for instance in consequence of probe replacement, then act in the following way: get an accurate
reference thermometer or calibrator; make sure that the 

offset oSx

of the 

probe

to be 

re-calibrated is 00

; switch off then on the unit. During

the self check (5 seconds from power-up), press  + + . When the re-calibration function is active choose the desired section by means of 

or

0A1

and 

0A2

allow 0°C calibration of the respective probe. 

SA1

and 

SA2

allow high temperature calibration to rectify a gain error. After

selecting the desired parameter, press  +

or 

to match the read-out value with the one of the reference instrument (make sure the temperature

is stable).
Exit from the recalibration occurs after 10 seconds of no key activation. Therefore, to avoid exit, keep 

pressed for as long as you need. 

10. SERIAL COMMUNICATION

If fitted, the RS485 serial port allows the CDC12 to take part as a peripheral in a data communication network managed by a master PC supervisor.
The data base puts all measurement and control data on line as well as the output status. 

Adr

is the unit identification number within the network.

Through the serial communication it’s possible to change all control parameters (setpoint and SETUP), start defrost cycles, put the controller on a
standby or inhibit the controller keypad in order to avoid unauthorised access to programming function. 

WARRANTY

LAE electronic Srl warrant that their products are free of any defects in workmanship and materials for a period of 1 (one) year from date of production
shown on the enclosure. LAE electronic Srl shall only repair or replace those products of which defects are due to LAE electronic Srl and recognised by their
technicians. LAE electronic Srl are not liable for damages resulting from malfunctions of the products.
Defects due to exceptional operating conditions, misapplication and/or tampering will void the warranty.
All transport charges for returning the product to the manufacturer, after prior authorisation by LAE electronic Srl, and for the return to the purchaser are
always for the account of the purchaser.

INSTRUCTIONS FOR INSTALLATION AND USE.

Summary of Contents for CDC122T1R2

Page 1: ... about the relay contact life Where delicate or valuable products have to be maintained under strict conditions please use a different controller for limit and alarm functions 2 CONTROL PARAMETERS The adaptation of the CDC 12 to the system that it controls is achieved through the parameters in the SETUP Access to the parameters is obtained by pressing for 4 seconds Scroll through the parameters by...

Page 2: ...e cooler run isn t controlled according to setpoint but determined by cdc which represents the cooler duty cycle i e on time 10 minute cycle For ex 04 4 minutes on time 6 minutes off time The cdc value has to be set taking into consideration the normal cooler duty cycle If you wish to switch off the outputs you can put the CDC12 on a standby via the serial communication or manually by pressing dur...

Page 3: ...s case the condition must be acknowledged by pressing any key The alarm output contact is also closed when the instrument is powerless During defrost and dripping the high alarm monitoring is inhibited 9 PROBE RE CALIBRATION Should it be necessary to recalibrate the unit for instance in consequence of probe replacement then act in the following way get an accurate reference thermometer or calibrat...

Page 4: ...150 20 3 hyS 01 20 02 4 coF 00 10 00 5 con 00 10 00 6 cdc 00 10 05 7 crS 00 120 00 8 drE 01 99 06 9 dLi 01 70 10 10 dto 01 120 30 11 drP 00 10 03 12 diS 01 30 10 13 dty FAn ELE GAS ELE 14 doP con Acc con 15 Fct 01 00 10 01 16 FrS 50 150 10 17 Fid 00 01 02 00 18 Alo 50 150 32 19 Ahi Alo 150 22 20 AdL 01 00 120 10 21 Ain 1 2 3 01 22 oS1 20 20 00 23 oS2 20 20 00 24 oS3 20 20 00 25 SiM 00 200 00 26 Ad...

Reviews: