UNIT WILL HAVE A TURN ON DELAY OF 2 MIN, TO CHANGE
MODIFY "CRT"
AT2 LAE PARAMETERS
AT2 PARA
LRC VALUES
DESCRIPTION
SCL
F READOUT SCALE
SPL
0 MIN SE TPOINT TEMPERATURE
SPH
100 MAX SE TPOINT TEMPERATURE
SP
53 SET POINT
C-H
REF CONTROL MODE
HYS
2 THERMOSTAT DIFFERENTIAL
CRT
2 COMPRESSOR REST TIME
CT1
4 CYCLE TIME ON (WHEN T1 PROBE FAILS)
CT2
6 CYCLE TIME OFF (WHEN T1 PROBE FAILS)
CSD
0 COMPRESSOR STOP DELAY, WHEN USING DOOR SENSOR
DTY
OFF DEFROST TYPE
FID
YES FANS ACTIVE DURING DEFROST
FDD
0 EVAPORATOR FAN RESTART TIME
FTC
NO OPTOMISED FAN CONTROL
FT1
0 FAN STOP DELAY
FT2
0 TIMED FAN STOP
FT3
0 TIMED FAN RUN
ATM
NON ALARM THESHOLD MANAGEMENT
ADO
0 DELAY BEFORE DOOR OPEN ALARM
ACC
0 CONDENSER CLEANING REMINDER (WEEKS)
IISM
NON ENABLE SECOND PARAMETER SET
SB
YES STANBY ENABLED
DS
NO DOOR SWITCH INPUT ENABLED
LSM
NON LIGHT CONTROL MODE
OAU
NON AUX OUTPUT OPERATION
INP
SN4 TEMPERATURE TYPE
OS1
0 PROBE T1 OFFSET
T2
NO PROBE T2 ENABLE
OS2
0 PROBE T2 OFFSET
TLD
1 DELAY FOR MIN TEMP AND MAX TEMP LOGGING
SIM
0 DISPLAY SLOWDOWN