background image

 

 

INSTRUCTIONS FOR THE INSTALLER 

 

 

2.  

 

Figure No.6 -

 

Exterior diagram of the 

casing 

In  order  to  enable  suitable  air 

circulation  and  correct  operation,  the 
casing  must  have  a  fresh-air  inlet  with  a 
minimum section of 1,000cm

2

 beneath the 

level  of  the  actual  appliance  and  a  hot-air 
outlet measuring at least 1,000cm

2

 above it 

(just  before  the  insulating  deflector  inside 
the casing). These inlet and outlet sections 
must ensure air renewal in such a way as to 
avoid damage to parts inside the hood due 
to excess temperature. 

This  specification  must  be  observed 

regardless  of  the  type  of  installation 
chosen (with or without forced ventilation, 
combustion  air  from  indoors  or  outdoors, 
directed  hot-air  outlets  with  or  without 
pipes,  etc.).  A  further  hot-air  ventilation 
grille  is  also  recommended  between  the 
insulating  deflector  on  the  hood  and  the 
ceiling. 

As well as this, the hood/closure should 

have a free opening of at least 100 cm2 for 

the intake of air for combustion. 

On 

non-central-heating 

appliances 

(without  back  boiler),  Lacunza  does  not 

recommend  enveloping  the  outside  of 
appliances with insulation. 

Never completely block off the lateral 

ventilation grilles of the fairing. 

The  installer  must  fit  the  necessary 

inspection  accesses  (trap  doors,  hatches, 
etc.)  so  that  everything  inside  the  hood 
that  may  need  maintenance  work  or 
replacement  can  be  accessed  at  any  time, 
e.g.  counterweight  system,  hydraulic 
components, 

heating 

circuit 

safety 

components. 

2.3.6.

 

Connection to the flue 

The appliance must be connected to the 

chimney flue  using special piping designed 
to  resist  the  products  of  combustion  (e.g. 
stainless steel, enamelled steel, etc.). 

To connect the flue to the socket flange, 

insert the piping inside the flange and seal 
the joint with fire sealant or fire cement to 
make it completely airtight. 

The  installer  must  ensure that  the  pipe 

connected to the appliance is well secured 
and  there  is  no  chance  of  it  coming  free 
from  its  housing  (e.g.  as  a  result  of 
dilatation due to temperature, etc.). 

2.3.7.

 

Piping air to other rooms 

It  is  possible  to  pipe  some  of  the  heat 

generated  to  other  rooms  in  the  house 
using  the  appliance.  This  does  not  mean 
that  the  appliance  works  more  efficiently, 
but it does mean that the heat it creates is 
distributed better. For this purpose,  in the 
top  surface  of  the  appliance  there  are  2 
potential  hot-air  outlets  with  diameters  of 
120mm  on  the  top  shell  of  the  appliance. 
Pipes  can  be  fitted  from  these  outlets  to 
other rooms. If you intend to do this, bear 
the following points in mind. 

 

The  air  ducts  must  always  be  heat 

insulated  and  smooth  inside  (not 
corrugated). 

Summary of Contents for IF-800

Page 1: ...IV 800 Instruction Book ...

Page 2: ...1 Warning to installers 5 2 2 Room for installation 5 2 2 1 Ventilation of the room 5 2 2 2 Location of the appliance in the room 6 2 3 Installation of the appliance 6 2 3 1 Floor 6 2 3 2 Safety distances 6 2 3 3 Checks before lighting for the first time 6 2 3 4 Height adjustment and levelling the appliance 6 2 3 5 Casing 7 2 3 6 Connection to the flue 8 2 3 7 Piping air to other rooms 8 2 3 8 Ext...

Page 3: ... 4 1 1 Firebox 20 4 1 2 Flue socket 20 4 1 3 Painted sheet steel cast iron parts 20 4 1 4 Firebox glass 20 4 1 5 Electrical system 20 4 1 6 Air intake registers 20 4 2 Maintenance of the chimney flue 20 4 3 Important advice 21 TROUBLESHOOTING 22 BASIC BREAKDOWNS 23 DECLARATION OF PERFORMANCE 24 CE MARK 26 ...

Page 4: ...legislation applicable in each country and this instruction book 1 1 General characteristics Unit IV 800 Nominal Heat Output N H O to atmosphere kW 8 5 Efficiency at N H O 78 CO emission at 13 O2 at N H O 0 07 Gas mass flow at N H O g s 9 6 Gas temperature of flue at N H O ºC 238 Gas temperature on the flue socket flange ºC 286 Optimum flue draught Pa 12 Wood consumption beech at N H O Kg h 2 7 Di...

Page 5: ...idity of the fuel fuel loads fuel load frequencies flue draught and system of installation indicated in this Instruction Book Failure to respect these conditions may lead to problems with the appliance deterioration shorter useful life etc which are not covered by the Lacunza warranty Figure No 1 Dimensions of the IV 800 in mm ...

Page 6: ...olutely crucial to ensure the suitable renewal of the air in the room in which the appliance is fitted the room must always have at least two permanent grilles or openings to the exterior in order to renew the air one for intake and the other for extraction For the installation of its appliances Lacunza recommends an additional section for these openings One of these two grilles must be situated h...

Page 7: ... the left hand side 400 From the rear 400 From the front 1000 Bear in mind that it may even be necessary to protect non combustible material in order to prevent breakage deformation etc as a result of overheating if the non combustible material is not designed to withstand high temperatures 2 3 3 Checks before lighting for the first time Make sure that the glass es is are not broken or damaged Mak...

Page 8: ...how the appliance can be encased properly Figure No 5 Interior diagram of the casing Key to casing diagram 1 Ceiling 2 Flue 3 Incombustible material Inner hood insulation 4 Insulating deflector made of incombustible material 5 Wall 6 Fresh air inlet 1 000 cm2 7 Hot air outlet 1 000 cm2 ...

Page 9: ...fit the necessary inspection accesses trap doors hatches etc so that everything inside the hood that may need maintenance work or replacement can be accessed at any time e g counterweight system hydraulic components heating circuit safety components 2 3 6 Connection to the flue The appliance must be connected to the chimney flue using special piping designed to resist the products of combustion e ...

Page 10: ...he appliance working at Nominal Heat Output Output kW IV 800 2 5 Note The values shown in the above table were measured at the appliance output point and based on tests performed at nominal heat output and maximum fan speed All hot air ducts lose heat meaning that the heat output obtained at the end of piping always depends on its design This insert has serial air outputs If we wish to position th...

Page 11: ...an be used to attach it to the apparatus This should be done as follows Loosen without removing the two screws on the upper support of the door with a 10 mm wrench By lifting this piece up the door can be removed to provide comfortable access to the fastening points of the frame Figure No 9 Loosening the door support with a 10 mm wrench Fasten the 6 screws provided using an L shaped Torx T20 wrenc...

Page 12: ...ual Due to the movement of the ventilators this apparatus may vibrate structures that come into contact with it These vibrations may cause noise To prevent these vibrations from occurring a damping element that is also resistant to high temperatures up to 200ºC should be positioned between the base of the apparatus and the supporting structure 2 4 Chimney flue The chimney flue must comply with pre...

Page 13: ...nimum Each 45º bend is equivalent to a 0 5m reduction in flue length Horizontal flue sections should not be installed because they cut updraught a great deal If the flue draws at more than 20Pa then an effective damper must be fitted on the flueway This damper must be visible and accessible The chimney flue must not rest on the appliance Bear in mind that high temperatures may be reached in the fl...

Page 14: ...tacle located within a 10m radius of the chimney outlet by more than 1m Figure No 16 Distances between the chimney crown and objects within a 10m radius The chimney crown must clear any neighbouring building or obstacle located within a radius of 10m to 20m from the chimney outlet Figure No 17 Distances between the chimney crown and objects within a radius of between 10 and 20m ...

Page 15: ...ely chopped wood produces greater heat output but also burns more quickly Optimum fuels Beech Other fuels Oak chestnut ash maple birch elm etc Pine and eucalyptus logs are low density and produce very long flames and may cause the parts of the appliance to wear out more quickly than normal Resinous wood may mean that the appliance and the flue need to be cleaned more often Non permitted fuels All ...

Page 16: ...arm weather warm days early hours of the afternoon on sunny days may lead to lighting and updraught problems Certain weather conditions such as fog ice humidity entering the flue etc may hinder sufficient updraught in the flue and lead to suffocation Proceed as follows in order to light the appliance satisfactorily Open the firebox door s and open all the firebox air intake inlets to the full Plac...

Page 17: ...inutes Always load with the nominal amount see table in section 1 1 For minimum burning e g at night use thicker logs When the firebox is loaded close the door Be careful when placing logs in the firebox on appliances with vermiculite interiors Vermiculite is a fragile material and may crack if knocked 3 5 Operation The appliance should be operated with the door closed For safety reasons never clo...

Page 18: ...he released hatch position In order to fill the complete capacity of the ashpit box shake it back and forth Remove the separator This way there is even greater access to push the ashes from the firebox into the ashpit box Figure No 2 Removing the separator Figure No 3 Removed separator In order to fill the complete capacity of the ashpit box shake it back and forth Extract the ashpit box cold or u...

Page 19: ... cooking grille is an element to be used intermittently The grille is not designed to work non stop over the fire Never close the door with the handles inside the firebox These handles should only be used when the grille is being moved 3 8 Deflectors The appliance has 2 vermiculite deflectors and a stainless steel reinforcement that joins them together Dismantling the Ocean deflector First extract...

Page 20: ...he mains electricity supply in accordance with the conditions described in the relevant section in 1 1 Potentiometer operation By means of its rotating lever the potentiometer controls the flow of hot air output from the appliance Automatic mode The fan automatically starts working at the set speed via the thermostat When a fire has been lit in the firebox and the thermostat reaches a temperature ...

Page 21: ...r for longer However the glass may get dirty the longer the appliance is used Special degreasing products designed for the purpose should be used to clean it Clean when the glass is cold and taking care not to apply the glass cleaner directly onto the glass as it could come into contact with the door seal cord and damage it 4 1 5 Electrical system The electrical system should be cleaned vacuumed r...

Page 22: ...rebox block the connection hole with damp cloths and call the fire brigade 4 3 Important advice Lacunza recommends that only Lacunza authorised replacement parts be used Lacunza accepts no liability for any modification to the product which it has not authorised This appliance is a heat producing appliance and contact may lead to burns This appliance may remain HOT for a period of time after it ha...

Page 23: ...hips carpentry scraps plywood pallets etc Cold flue Heat up the flue by burning a piece of paper in the firebox Smoke during burning The room is at low pressure In rooms with Controlled Mechanical Ventilation leave an outdoor window ajar until the fire is fully alight Too little wood loaded Load as recommended Loads notably smaller than those recommended lead to low smoke temperature and downdraug...

Page 24: ...undición IF 800 1 9 5044400000 IV 800 Deflector vermiculita IZQ DCHO 2 10 5044400001 IV 800 Angulo sujeción deflector 1 11 504420000011 Pieza móvil registro primario IF 800 1 12 504420000012 Pieza móvil registro secundario IF 800 1 13 509020000042 Cordón Negro Ø13mm 3m 14 500000000510 Cordon plano pelos 8x2mm 3m 15 504430000000 Vermiculita lateral izda delantera IV 800 1 16 504430000001 Vermiculit...

Page 25: ...DECLARATION OF PERFORMANCE 24 7 DECLARATION OF PERFORMANCE ...

Page 26: ...DECLARATION OF PERFORMANCE 25 7 ...

Page 27: ...CE MARK 26 8 CE MARK ...

Page 28: ...LACUNZA KALOR GROUP S A L Pol Ind Ibarrea s n 31800 Alsasua Navarra Spain Tel 00 34 948 56 35 11 Fax 00 34 948 56 35 05 e mail comercial lacunza net Website www lacunza net EDITION 0 ...

Reviews: