INSTRUCTIONS FOR THE INSTALLER 

 

 

2.  

 

INSTRUCTIONS FOR THE 

INSTALLER  

2.1.

 

Warning to installers 

All  local  and  national  regulations, 

including all those referring to national and 
European  standards,  must  be  observed 
when installing the appliance. 

Installation  of  the  appliance  must  be 

performed by an authorised installer. 

An  incorrectly  installed  appliance  may 

lead  to  serious  incidents  (fires,  creation  of 
harmful  gases,  deterioration  of  nearby 
fixtures, etc.). 

Lacunza’s  liability  is  limite

d  to  the 

supply of the material and does not include 
installation of the appliance. 

2.2.

 

Room for installation 

2.2.1.

 

Ventilation of the room 

The  appliance  needs  to  consume 

oxygen  (air)  in  order  to  work  properly. 
Ensure a suitable air supply in the room in 
which the appliance is fitted. This quantity 
of  oxygen  is  additional  to  the  oxygen  that 
we need in order to breathe (air renewal).  

In  order  to  ensure  the  high  quality  of 

the  air you breathe and to avoid potential 
accidents 

resulting 

from 

high 

concentrations  of  the  gases  produced  by 
combustion  (mainly  carbon  dioxide  and 
carbon monoxide), it is absolutely crucial to 
ensure  the  suitable  renewal  of  the  air  in 
the room in which the appliance is fitted. 

the room must always have at least two 

permanent  grilles  or  openings  to  the 
exterior in order to renew the air (one  for 
intake and the other for extraction). 

For  the  installation  of  its  appliances, 

Lacunza recommends an additional section 
for these openings. One of these two grilles 
must  be  situated  high  up  in  the  room  (at 

less  than  30  cm  from  the  ceiling)  and  the 
other  one  low  down  (at  less  than  30  cm 
from  the  floor).  Both  grilles  must  open 
outdoors  in  order  to  renew  the  air  in  the 
room with fresh air. 

The minimum section that each of these 

grilles  must  have  depends  on  the  nominal 
output of the appliance in accordance with 
the following table: 

 

 

 

Figure No.2 -

 

Guideline indications for 

ventilation grilles 

The appliance must always be used with 

the door(s) closed.  

In  rooms  equipped  with  Controlled 

Mechanical 

Ventilation, 

the 

system 

extracts  and  renews  the  ambient  air;  in 
such  cases,  the  room  is  at  slightly  low 
pressure and it is necessary to install a non-
closable  outside-air  inlet  with  a  section  of 
at least 90 cm². 

Output of the 

appliance 

(kW)

Minimum 

additional section 

of each of the 

grilles (cm

2

)

P ≤ 10kW

70

10 < P ≤ 15

90

15 < P ≤ 20

120

20 < P ≤ 25

150

25 < P ≤ 30 

180

30 < P ≤ 35 

210

P > 35

240

Summary of Contents for AUSTRALIA Atlantic 610

Page 1: ...Atlantic 610 Instruction Book AUSTRALIA ...

Page 2: ...PRESENTATION OF THE APPLIANCE 1 1 ...

Page 3: ...TALLER 6 2 1 Warning to installers 6 2 2 Room for installation 6 2 2 1 Ventilation of the room 6 2 2 2 Location of the appliance in the room 7 2 3 Installation of the appliance 7 2 3 1 Floor 7 2 3 2 Safety distances 7 2 3 3 Checks before lighting for the first time 7 2 3 4 Height adjustment and levelling the appliance 8 2 3 5 Connection to the flue 8 2 4 Chimney flue 8 2 4 1 Type of flue 8 2 4 2 C...

Page 4: ...NCE 3 1 4 1 3 Flue socket 16 4 1 4 Painted sheet steel cast iron parts 16 4 1 5 Firebox glass 16 4 2 Maintenance of the chimney flue 16 4 3 Important advice 17 TROUBLESHOOTING 18 BASIC BREAKDOWNS 19 CERTIFICATE OF COMPLIANCE 20 ...

Page 5: ...TPUT BURNING HARDWOOD kW 9 1 OVERALL AVERAGE EFFICIENCY BURNING HARDWOOD 64 PARTICULATE EMISSIONS FACTOR g kg 0 5 HIGH BURN Average power high primary air settings kW 9 1 Average Peak Power kW 11 8 Efficiency high primary air settings 58 Average dry fuel consumption rate high primary air settings Kg hr 2 9 Particulate emission factor oven dry wood high primary air settings g kg 0 3 MEDIUM BURN Ave...

Page 6: ...f installation indicated in this Instruction Book Failure to respect these conditions may lead to problems with the appliance deterioration shorter useful life etc which are not covered by the Lacunza warranty To obtain these data tests have been done on the standards AS NZS 4012 2014 AS NZS 4013 2014 and AS NZS 2918 2018 with eucalyptus wood Figure No 1 Dimensions of the Atlantic 610 appliance in...

Page 7: ...olutely crucial to ensure the suitable renewal of the air in the room in which the appliance is fitted the room must always have at least two permanent grilles or openings to the exterior in order to renew the air one for intake and the other for extraction For the installation of its appliances Lacunza recommends an additional section for these openings One of these two grilles must be situated h...

Page 8: ...appliance door and be placed centrally in the 920mm width The Thermal resistivity of the floor protector is 0 078m K W for 18mm thick compressed board sheets Combustible material cannot be stored closer than 50mm below the firebox in wood storage area 2 3 2 Safety distances Be sure to respect the appliance installation distances from combustible materials Bear in mind that it may even be necessary...

Page 9: ...pliances without back boiler require an insulated double sleeve flue only on those sections that run outdoors or through cold areas Single piping can be used inside the building the heat of the gases serving to heat rooms insulating only those sections where excess temperature may cause damage If the chimney is constructed then it is necessary to pipe and insulate it to ensure correct updraught Th...

Page 10: ... withstand high temperatures It must be possible to clean the entire flue no sections being left inaccessible for cleaning purposes 2 4 2 Chimney crown The upper end of the chimney must clear the roof the roof ridge or any obstacle located on the roof by at least 1m Figure No 3 Distances between chimney crown and roof ridge The chimney crown must clear the highest point of any neighbouring buildin...

Page 11: ... the material insulation diameter airtightness cleanliness height verticality straightness chimney crown etc If sufficient updraught is not achieved by correcting the flue installation Lacunza supplies an accessory for exceptional cases a part which seals the top of the front part of the appliance and helps prevent smoke escaping into the room Logically this reduces both the view of the fire and t...

Page 12: ... stored The logs should have a maximum diameter of 150mm Finely chopped wood produces greater heat output but also burns more quickly Optimum fuels Beech hardwood and eucalyptus logs Other fuels Oak chestnut ash maple birch elm etc Resinous wood may mean that the appliance and the flue need to be cleaned more often Non permitted fuels All types of coal and liquid fuel Green wood Green or damp wood...

Page 13: ...of the appliance 3 2 1 Operating components Figure No 8 Operating components on the appliance A Firebox door handle B Primary air intake o B1 open right o B2 closed left C Secondary air intake o C1 open right o C2 closed left D Double combustion air intake ...

Page 14: ...no longer appear when the appliance has been lit three or four times and has adapted to its flue If it does not disappear then check the flue draught length and diameter of the flue flue insulation airtightness and the humidity of the wood used 3 4 Safety Do not store combustible materials beneath the appliance 3 5 Loading fuel In order to load firewood open the firebox door gently preventing the ...

Page 15: ...utput open all the air intakes to the firebox and in order to obtain minimum output tend towards closing them For normal use we recommend you close the Primary Intake and leave the Secondary and Double Combustion Intakes open a High burn rate The appliance shall be operated with combustion rate controls fully open b Low burn rate The appliance shall be operated with all combustion rate controls ad...

Page 16: ...e reinforcement In order to do this draw it towards the front of the appliance to release it from the vermiculite parts Figure No 11 First movement to release the reinforcement The vermiculite deflectors can then be extracted as shown Figure No 12 Extracting the vermiculite deflectors Extract the rest of the firebox vermiculite Figure No 13 Extract the rest of firebox vermiculites Figure No 14 Tur...

Page 17: ... this task The cleaning should be carried out with the glass cold and taking care not to apply the glass cleaner directly on the glass as if it comes into contact with the door s closing cord it may deteriorate Put the cleaning product on the cloth Caution the vitro ceramic glass is prepared to support 700ºC Never let burning woods or combustion flame beating against the glass for prolonged period...

Page 18: ...ll the fire brigade 4 3 Important advice Lacunza recommends that only Lacunza authorised replacement parts be used Lacunza accepts no liability for any modification to the product which it has not authorised This appliance is a heat producing appliance and contact may lead to burns This appliance may remain HOT for a period of time after it has gone out MAKE SURE THAT SMALL CHILDREN DO NOT GO NEAR...

Page 19: ... continually burn chips carpentry scraps plywood pallets etc Cold flue Heat up the flue by burning a piece of paper in the firebox Smoke during burning The room is at low pressure In rooms with Controlled Mechanical Ventilation leave an outdoor window ajar until the fire is fully alight Too little wood loaded Load as recommended Loads notably smaller than those recommended lead to low smoke temper...

Page 20: ...026700014 Separador Ocean 1 6 Atlantic 610 Australia pieza móvil registro primario 1 7 Atlantic 610 Australia pieza móvil registro secundario 1 8 5000000945 Refuerzo deflector 1 9 502670000002 Cristal hogar Ocean 610 610R 1 502670000003 Cristal hogar Atlantic 610 610R 1 10 509020000042 Cordón Negro Ø13mm 3m 11 500000000510 Cordón plano pelos 8x2mm 2m 12 5040000904 Nickel Adour Parrilla hogar 1 13 ...

Page 21: ...CERTIFICATE OF COMPLIANCE 20 7 CERTIFICATE OF COMPLIANCE ...

Page 22: ...CERTIFICATE OF COMPLIANCE 21 7 ...

Page 23: ...CERTIFICATE OF COMPLIANCE 22 7 ...

Page 24: ......

Page 25: ...LACUNZA KALOR GROUP S A L Pol Ind Ibarrea s n 31800 Alsasua Navarra Spain Tel 00 34 948 56 35 11 Fax 00 34 948 56 35 05 e mail comercial lacunza net Website www lacunza net EDITION 0 ...

Reviews: