background image

6

 

 

Refrigerator

 

Operation

 

After

 

the

 

unit

 

is

 

properly

 

installed

 

and

 

power

 

is

 

applied,

 

it

 

will

 

take

 

some

 

time

 

before

 

the

 

system

 

is

 

cooled

 

down

 

to

 

temperature

 

and

 

cycling

 

normally.

 

You

 

should

 

wait

 

8

 

hours

 

on

 

the

 

first

 

startup

 

before

 

beginning

 

to

 

add

 

product

 

to

 

the

 

unit.

 

This

 

ensures

 

that

 

the

 

unit

 

is

 

installed

 

and

 

operating

 

properly

 

before

 

being

 

put

 

into

 

service.

 

On

 

subsequent

 

startups

 

(after

 

cleanings,

 

for

 

example),

 

this

 

wait

 

time

 

can

 

be

 

reduced

 

to

 

about

 

3

 

hours.

   

After

 

this

 

wait

 

time,

 

the

 

unit

 

should

 

be

 

cycling

 

in

 

the

 

design

 

temperature

 

range.

 

The

 

units

 

are

 

calibrated

 

before

 

leaving

 

the

 

factory,

 

so

 

no

 

adjustment

 

should

 

be

 

necessary.

  

Loading

 

the

 

units

 

will

 

again

 

cause

 

temperature

 

to

 

rise

 

as

 

the

 

warmer

 

product

 

is

 

introduced

 

into

 

the

 

compartment.

 

If

 

a

 

large

 

amount

 

of

 

product

 

is

 

to

 

be

 

introduced,

 

it

 

is

 

a

 

good

 

idea

 

to

 

do

 

it

 

in

 

stages,

 

allowing

 

several

 

hours

 

between

 

stages

 

to

 

allow

 

temperature

 

to

 

stabilize

 

again

 

before

 

introducing

 

additional

 

warm

 

product.

 

This

 

will

 

minimize

 

the

 

temperature

 

transient

 

while

 

loading.

 

Other

 

tips

 

for

 

successful

 

loading

 

include:

  

 

Leave

 

about

 

2

3

 

inches

 

of

 

free

 

space

 

along

 

the

 

back

 

and

 

sides

 

of

 

the

 

unit

 

to

 

allow

 

for

 

proper

 

air

 

flow

 

and,

 

therefore,

 

more

 

even

 

cooling

 

of

 

the

 

product.

  

 

When

 

loading

 

the

 

top

 

shelf,

 

avoid

 

blocking

 

the

 

evaporator

 

fan(s)

 

(if

 

installed).

 

There

 

should

 

be

 

at

 

least

 

4

 

inches

 

of

 

clearance

 

below

 

the

 

fan(s)

 

to

 

allow

 

proper

 

air

 

flow.

  

 

Do

 

not

 

overload

 

the

 

unit.

 

A

 

full

 

load

 

is

 

about

 

70

 

to

 

75%

 

full.

 

Additionally,

 

the

 

load

 

should

 

be

 

distributed

 

evenly

 

from

 

top

 

to

 

bottom

 

and

 

side

 

to

 

side

 

for

 

best

 

results.

  

 

Minimize

 

the

 

time

 

the

 

door

 

is

 

open.

 

On

 

top

 

of

 

letting

 

the

 

cold

 

air

 

out,

 

you

 

are

 

also

 

letting

 

warm,

 

moist

 

air

 

in

 

which

 

can

 

result

 

in

 

more

 

condensation

 

and/or

 

frost

 

in

 

the

 

unit.

  

The

 

auto

defrost

 

models

 

will

 

periodically

 

(usually

 

2

 

to

 

4

 

times

 

a

 

day)

 

go

 

into

 

a

 

defrost

 

cycle

 

to

 

remove

 

frost

 

build

up

 

around

 

the

 

evaporator

 

coils.

 

During

 

this

 

cycle,

 

the

 

compressor

 

is

 

turned

 

off

 

and

 

defrost

 

heaters

 

are

 

turned

 

on

 

in

 

the

 

evaporator

 

section.

 

This

 

will

 

cause

 

a

 

temperature

 

transient

 

which

 

will

 

be

 

seen

 

in

 

air

 

temperature

 

inside

 

the

 

unit

 

but

 

should

 

not

 

significantly

 

affect

 

product

 

temperatures.

  

Remember

 

that

 

the

 

units

 

are

 

calibrated

 

to

 

the

 

design

 

temperature

 

range

 

before

 

leaving

 

the

 

factory.

 

We

 

also

 

do

 

extensive

 

testing

 

to

 

ensure

 

that

 

these

 

temperatures

 

will

 

result

 

in

 

product

 

temperatures

 

in

 

the

 

desired

 

band.

 

There

 

should

 

be

 

no

 

need

 

to

 

adjust

 

the

 

temperature

 

control

 

on

 

these

 

units,

 

but

 

if

 

it

 

is

 

necessary,

 

they

 

can

 

be

 

adjusted

 

using

 

the

 

manual

 

thermostat

 

on

 

the

 

inside

 

of

 

the

 

unit

.

  

It

 

is

 

STRONGLY

 

RECOMMENDED

 

that

 

you

 

contact

 

the

 

manufacturer’s

 

Technical

 

Support

 

Department

 

prior

 

to

 

performing

 

any

 

temperature

 

adjustments

 

to

 

ensure

 

the

 

adjustment

 

is

 

necessary

 

and,

 

if

 

so,

 

it

 

is

 

performed

 

correctly.

  

Summary of Contents for LABH?14?SD

Page 1: ...of delivery Make sure you get a signed copy Send a written request for an inspection to the carrier B Concealed Damage This type of damage may not be discovered until the unit is being unpacked When...

Page 2: ...unit s model and serial number ready as well as the problem description The model and serial number is located on the serial tag which can be found on the interior left upper wall of the unit For conv...

Page 3: ...knowledging the damage This has to happen at the time of delivery or it won t happen at all Keep a copy for your records and send another to the carrier s damage claims department along with a formal...

Page 4: ...ecommended to prevent possible loss of product due to over loading or failure of other equipment on the same circuit PROTECT THE CIRCUIT WITH A 20 AMP DELAY TYPE FUSE OR CIRCUIT BREAKER Do not use an...

Page 5: ...ory to provide the desired air and product temperatures inside of the unit and requires no further adjustment Please contact the manufacturer s Technical Support Department before making any adjustmen...

Page 6: ...fan s if installed There should be at least 4 inches of clearance below the fan s to allow proper air flow Do not overload the unit A full load is about 70 to 75 full Additionally the load should be...

Page 7: ...ount of stored product is overloaded Product replacements are pushed against rear wall or interrupted the proper refrigerator air circulation For the proper air circulation place the products evenly o...

Page 8: ...left upper wall of the unit PROBLEM POSSIBLE CAUSE SOULTIONS Compressor noises Compressor may be overheated Please check the room temp and ensure the range is within 65 F to 85 F If the problem still...

Page 9: ...ry Door Gaskets Soap and water Wipe gaskets and their seating surfaces with a clean soft cloth Shelves Soap and water Do not wash removable shelves in dishwasher Exterior and Handles Soap and water No...

Page 10: ...ion of the original warranty ADDITIONAL THREE YEAR COMPRESSOR WARRANTY In addition to the two 2 year warranty stated above Horizon Scientific Inc warrants its hermetically and semi hermetically sealed...

Page 11: ...te of manufacture to alteration neglect abuse misuse accident damage during transit or installation fire flood or other external causes It does not apply to defects resulting from failure to properly...

Reviews: