Laboratorio Electrotecnico AEP-7 User Manual Download Page 3

 

2/6 

 

User Manual

 

 

 
 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

 
 
 
 

 

 

3. INSTALLATION  

3.1 Assembly 

Indoor equipment can be mounted in any position, taking all the precautions and abiding by legal 
or regulatory provisions. 
Outdoor equipment must only be mounted in upright position. 
VKE type models must be handled correctly in order not to damage the outer metal coating. The 
transformer must be repaired if there is visible deterioration. 
 

3.2 Installation 

The equipment is intended to be installed in networks with neutral to  earth (earth fault factor 

 

1.4).  In  the  event  that  the  neutral  system  was  not  effectively  grounded,  consult  Laboratorio 
Electrotécnico for the possibility of installing the equipment. 

Instrument  transformers  must  be  installed  in  appropriate  places  such  as  fenced  substations, 
buildings,  modules  with  enclosures  or  similar,  that  do  not  allow  access  to  dangerous  parts  by 
people and that protect the equipment against foreign objects. 

They must also be installed so that no person can access them without first disconnecting the line 
that feeds them to access safely by controlled means (blockages, operating procedures, etc.). 
 

3.3 Connection 

All the terminals corresponding to the transformation ratios requested are properly and indelibly 
marked on the transformed surface, and reference is made to the necessary connection for each 
ratio on the equipment name plate. 

The equipment is supplied with all the necessary connection elements. 

The connections will be made as indicated on the name plate, taking special care when tightening 
the terminals, and in the provision of the ratio change connections for those current transformers 
that have them. 

The tightening torque of these terminals, depending on the metrics used, is given below: 

-  For M6 terminals 

 

2.5 N.m 

-  For M12 terminals   

 20 N.m 

-  For M10 terminals   

 11 N.m 

-  For M16 terminals    

        45 N.m 

 
Models VKE-24 and VKE-36 must be connected via the specific bushing. 
The  connection  between  the  bushing  and  the  transformer  is  made  by  pressure,  keeping  the 
contact parts as clean as possible and lubricated with non-conductive silicone. The bushing will 
be secured to the transformer via the hook or the screws supplied with it: 

 

Summary of Contents for AEP-7

Page 1: ...TAGE INSTRUMENT TRANSFORMERS D i v i s i n T r a n s f o r m a d o r e s s Passatge dels Rosers s n 08940 Cornell de Llobregat Barcelona ESPA A Phone 93 376 31 00 Fax 93 376 31 66 e mail lescop lescop...

Page 2: ...d or customer specification IEC 61869 Thermal short circuit current e g Ith 3 kA or 200 x In A in 1 sec Dynamic short circuit current 2 5 Ith unless otherwise specified Safety factor Fs for measuremen...

Page 3: ...ithout first disconnecting the line that feeds them to access safely by controlled means blockages operating procedures etc 3 3 Connection All the terminals corresponding to the transformation ratios...

Page 4: ...leave the secondary in short circuit as this could cause irreparable damage to the equipment Furthermore the n terminals must always be earthed 4 1 Models and weights The weights of standardised appli...

Page 5: ...until it is absolutely necessary The appliance comes with transport anchor points on the base which must be used to secure the transformer The appliance must be secured with a flexible transport elem...

Page 6: ...l 1 SECONDARY 2 SECONDARIES 1 SECONDARY WITH TAP 3 SECONDARIES P2 P1 P2 P1 C2 C1 C2 C1 2S2 2S1 P1 P2 1S2 1S1 P1 P2 S1 S2 S3 S2 P1 P2 S1 2S2 2S1 P1 1S2 1S1 P2 3S2 3S1 When S1 S3 is connected S2 must re...

Page 7: ...RIES 2n 2a A N 1n 1a 2 SECONDARIES 1 SEC for RESIDUAL VOLTAGE 2n 2a A 1n 1a N dn da 1 SECONDARY WITH TAP n a2 A N a1 RESIDUAL VOLTAJE SECONDARY CONNECTION da dn da dn da dn resistance Phase R Phase S...

Page 8: ...User Manual TRANSFORMERS DIVISION Passatge dels Rosers s n 08940 Cornell de Llobregat Barcelona ESPA A Telf 93 376 31 00 Fax 93 376 31 66 e mail lescop lescop com web www lescop com TR122019 0...

Reviews: